Plan Review Notes
Plan Review Notes For Permit 06050911
Permit Number 06050911
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-03 00:00:00 
  
 DENIED
  
 1) STRUCTURAL MULLION DESIGN REQUIRES
 MORE INFORMATION.
 A) HOW PLATE IS CONNECTED TO POST (NO
 WELD SPECIFIED)
 B) NO ELEVATION DETAIL, SHOW WHERE THE
 MULLION IS ATTACHED TOP AND BOTTOM AND
 THE STRUCTURE TO WHICH IT IS ATTACHED
 C) PROVIDE WIND DESIGN CRITERIA PER
 1603.1.4 FBC
 D) PROVIDE INFORMATION THAT DESIGN WILL
 MEET ALL LOAD CONDITIONS AND IS
 COMPATIBLE WITH A CURRENT STORE FRONT
 PRODUCT APPROVAL
 E) ENGINEER'S STAMP AND SIGNATURE IS ON
 THE BACK OF THE DRAWING
  
 ****NOTE DUE TO THE MANY DEFICIENCIES
 ONE COPY OF THIS DRAWING HAS BEEN
 RETAINED AND WILL BE FORWARDED TO THE
 FLORIDA BOARD OF PROFSIONAL ENGINEERS***
  
 2) PROVIDE STORE FRONT PRODUCT APPROVALS
 PLEASE BE SURE THAT THEY ARE LARGE
 MISSLE RATED (SOME ARE ONLY SMALL MISSLE
 RATED FOR USE ABOVE 30 FT)
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716