Plan Review Notes For Permit 06050890 |
Permit Number |
06050890 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-08-01 00:00:00 | | | | | PROVISO | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW PRIOR TO ROUGH INSPECTION. | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR | | THE DESIGN MUST PRINT AND SIGN THEIR | | NAME TO SAME PER 106.3.4.2. | | | | 2} PROVIDE A PANEL SCHEDULE PER 408.4. | | INLUDE WIRE AND BREAKER SIZES AND | | CIRCUIT NUMBERS. THE PANEL SHOWN ON THIS | | PLAN IS NONCOMPLIANT. | | | | NOTE: THE CIRCUIT NUMBER AT THE DEVICES | | ARE NOT REQUIRED FOR A RESIDENTIAL PLAN. | | IF THEY ARE PROVIDED THEY MUST CORRELATE | | WITH THE PANEL SCHEDULE. | | | | 3} LOCATE THE SERVICE EQUIPMENT ON THE | | PLAN. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | | | | | |
|