Plan Review Notes
Plan Review Notes For Permit 06050890
Permit Number 06050890
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-30 00:00:00 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PER 110.9 AND 110.10: OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.
  
 2} SHOW THE PHYSICAL LOCATION OF ALL
 SERVICE EQUIPMENT ON THE PLAN. 215.5.
  
 3} INDICATE COMPLIANCE WITH ARTICLE
 250.50 FOR THE GROUNDING ELECTRODE
 SYSTEM. ALL AVAILABLE MUST BE USED ON
 THE RISER. SIZE GEC PER 250.66.
  
 4} SMOKE DETECTORS MUST BE INSTALLED TO
 COMPLY WITH R313.1 RESIDENTIAL FLORIDA
 BUILDING CODE.
  
 5} KITCHEN RECEPTACLE SPACING MUST
 COMPLY WITH 210.52(A), 210.52(C), AND
 210.8(A)(6), GFI.
  
 6} 210.52(E) OUTDOOR OUTLETS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE
 THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. SEE 210.8(A)(3).
  
 7} G) BASEMENTS AND GARAGES. FOR A
 ONE-FAMILY DWELLING, AT LEAST ONE
 RECEPTACLE OUTLET, IN ADDITION TO ANY
 PROVIDED FOR LAUNDRY EQUIPMENT, SHALL BE
 INSTALLED IN EACH BASEMENT AND IN EACH
 ATTACHED GARAGE, AND IN EACH DETACHED
 GARAGE WITH ELECTRIC POWER. SEE
 210.8(A)(2).
  
 8} SHOW THE LOCATION OF THE A/C
 EQUIPMENT ON THE PLAN. ALSO SHOW
 COMPLIANCE WITH THE REQUIRED RECEPTACLE
 PER 210.63. DISCONNECT PER 440.14,
 110.26.
  
 THE PERSON TAKING RESPONSIBILITY FOR THE
 DESIGN MUST PRINT AND SIGN THEIR NAME TO
 SAME PER 106.3.4.2.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  