2006-05-30 00:00:00 | |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS |
| FOR CODE COMPLIANCE AND RESUBMIT FOR |
| REVIEW. |
| |
| 1} PER 110.9 AND 110.10: OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT. |
| |
| 2} SHOW THE PHYSICAL LOCATION OF ALL |
| SERVICE EQUIPMENT ON THE PLAN. 215.5. |
| |
| 3} INDICATE COMPLIANCE WITH ARTICLE |
| 250.50 FOR THE GROUNDING ELECTRODE |
| SYSTEM. ALL AVAILABLE MUST BE USED ON |
| THE RISER. SIZE GEC PER 250.66. |
| |
| 4} SMOKE DETECTORS MUST BE INSTALLED TO |
| COMPLY WITH R313.1 RESIDENTIAL FLORIDA |
| BUILDING CODE. |
| |
| 5} KITCHEN RECEPTACLE SPACING MUST |
| COMPLY WITH 210.52(A), 210.52(C), AND |
| 210.8(A)(6), GFI. |
| |
| 6} 210.52(E) OUTDOOR OUTLETS. FOR A |
| ONE-FAMILY DWELLING AND EACH UNIT OF A |
| TWO-FAMILY DWELLING THAT IS AT GRADE |
| LEVEL, AT LEAST ONE RECEPTACLE OUTLET |
| ACCESSIBLE AT GRADE LEVEL AND NOT MORE |
| THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL |
| BE INSTALLED AT THE FRONT AND BACK OF |
| THE DWELLING. SEE 210.8(A)(3). |
| |
| 7} G) BASEMENTS AND GARAGES. FOR A |
| ONE-FAMILY DWELLING, AT LEAST ONE |
| RECEPTACLE OUTLET, IN ADDITION TO ANY |
| PROVIDED FOR LAUNDRY EQUIPMENT, SHALL BE |
| INSTALLED IN EACH BASEMENT AND IN EACH |
| ATTACHED GARAGE, AND IN EACH DETACHED |
| GARAGE WITH ELECTRIC POWER. SEE |
| 210.8(A)(2). |
| |
| 8} SHOW THE LOCATION OF THE A/C |
| EQUIPMENT ON THE PLAN. ALSO SHOW |
| COMPLIANCE WITH THE REQUIRED RECEPTACLE |
| PER 210.63. DISCONNECT PER 440.14, |
| 110.26. |
| |
| THE PERSON TAKING RESPONSIBILITY FOR THE |
| DESIGN MUST PRINT AND SIGN THEIR NAME TO |
| SAME PER 106.3.4.2. |
| |