Plan Review Notes For Permit 06050889 |
Permit Number |
06050889 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-25 00:00:00 | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} 210.52(E) OUTDOOR OUTLETS. FOR A | | ONE-FAMILY DWELLING AND EACH UNIT OF A | | TWO-FAMILY DWELLING THAT IS AT GRADE | | LEVEL, AT LEAST ONE RECEPTACLE OUTLET | | ACCESSIBLE AT GRADE LEVEL AND NOT MORE | | THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL | | BE INSTALLED AT THE FRONT AND BACK OF | | THE DWELLING. SEE 210.8(A)(3). | | | | 2} INDICATE THE DISCONNECT FOR THE A/C | | AND UNIT LOCATTION. SHOW COMPLIANCE WITH | | 440.14 AND 210.62. | | | | 3} PROVIDE A RISER DIAGRAM WITH | | CONDUCTOR AND CONDUIT SIZE AND TYPE, | | GROUNDING DETAILS, LOAD CALCULATIONS, | | PANEL SCHEDULES, SERVICE EQUIPMENT AND | | PANEL LOCATIONS PER 106.3.5.4 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | WILLIAM R. TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561) 805-6718 | | | | |
|