Plan Review Notes
Plan Review Notes For Permit 06050889
Permit Number 06050889
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-25 00:00:00 
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} 210.52(E) OUTDOOR OUTLETS. FOR A
 ONE-FAMILY DWELLING AND EACH UNIT OF A
 TWO-FAMILY DWELLING THAT IS AT GRADE
 LEVEL, AT LEAST ONE RECEPTACLE OUTLET
 ACCESSIBLE AT GRADE LEVEL AND NOT MORE
 THAN 2.0 M (61/2 FT) ABOVE GRADE SHALL
 BE INSTALLED AT THE FRONT AND BACK OF
 THE DWELLING. SEE 210.8(A)(3).
  
 2} INDICATE THE DISCONNECT FOR THE A/C
 AND UNIT LOCATTION. SHOW COMPLIANCE WITH
 440.14 AND 210.62.
  
 3} PROVIDE A RISER DIAGRAM WITH
 CONDUCTOR AND CONDUIT SIZE AND TYPE,
 GROUNDING DETAILS, LOAD CALCULATIONS,
 PANEL SCHEDULES, SERVICE EQUIPMENT AND
 PANEL LOCATIONS PER 106.3.5.4 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  
  