2006-06-07 00:00:00 | DENIED |
| |
| |
| 1. 713.13 F.S.A NOTICE OF COMMENCEMENT |
| SHALL BE RECORDED AT PALM BEACH COUNTY |
| COURTHOUSE AND A COPY SUBMITTED TO THIS |
| OFFICE BEFORE A PERMIT CAN BE ISSUED. |
| BLANK FORMS ARE AVAILABLE FROM THIS |
| OFFICE. |
| NOTE: THE NOTICE OF COMMENCEMENT MUST BE |
| RE-RECORDED IF THE DESCRIBED IMPROVEMENT |
| OR CONSTRUCTION IS NOT COMMENCED WITHIN |
| 90 DAYS OF RECORDING. |
| |
| 2.BEFORE A PERMIT TO CONSTRUCT, MAY BE |
| ISSUED, IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 3.BASED ON ICC BUILDING VALUATION DATA |
| THE PERMIT VALUE HAS BEEN REVISED TO |
| $123,523.00.ADDITIONAL PERMIT FEES ARE |
| DUE. |
| |
| 4.PRODUCT APPROVALS REQUIRED FOR |
| EXTERIOR DOORS, LINTELS, AND STRAPS AND |
| TIE-DOWNS. |
| |
| 5.ALL PRODUCT APPROVALS SUBMITTED WITH |
| QUALITY ASSURANCE SHALL HAVE THE |
| FOLLOWING STATE APPROVAL ATTACHED. |
| |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A STATE PRODUCT APPROVAL |
| SHEETS THAT LISTS THE PRODUCT IDENTITY |
| NUMBER FROM THE STATE. IF THE PRODUCT |
| DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT |
| AN APPLICATION FOR LOCAL PRODUCT |
| APPROVAL OR SITE SPECIFIC FORM PER RULE |
| 9B-72. SEE ATTACHMENT. |
| WWW.FLORIDABUILDING.ORG |
| |
| 6.THOSE PRODUCT APPROVALS WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL.WPB |
| AMENDMENT TO FBC 106.3.3. |
| |
| 7.SUBMIT TWO SETS OF TRUSS DRAWINGS |
| FOR REVIEW PER 2004 FBC R-802.10.1 |
| |
| 8.PAGE 4 OF 5 NOT READABLE. |
| |
| 9.SHOW SIZE AND LOCATION OF ATTIC |
| ACCESS R807.1 |
| |
| 10.SHOW PLYWOOD SHEATHING NAILING |
| COMLYING WITH FBC 2304.9.1 #31 |
| |
| 11.R401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A |
| STORM SEWER CONVEYANCE OR OTHER APPROVED |
| POINT OF COLLECTION SO AS TO NOT CREATE |
| A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| WALLS. THE GRADE AWAY FROM FOUNDATION |
| WALLS SHALL FALL A MINIMUM OF 6 INCHES |
| WITHIN THE FIRST 10 FEET. |
| |
| 12.SUBMIT ONLY TWO SETS OF PLANS FOR |
| PERMITTING.PLEASE LEAVE PRODUCT |
| APPROVALLS DETACHED FROM PLANS. |
| |
| 13.MINIMUM DESIGN CRITERIA 106.35 WPB |
| AMMENDMENTS TO THE FBC.SHOW |
| CONSTRUCTION TYPE, AND DESIGN INFO ASCE |
| 7-02 |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| OLD PAGES FOR REFERENCE. A TRANSMITTAL |
| LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF |
| THE REVISION MADE, IDENTIFYING THE SHEET |
| OR SPECIFICATION PAGE WHERE THE CHANGES |
| CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| ART LANGE |
| CONSTRUCTION SERVICES DEPARTMENT |
| BUILDING PLANS EXAMINER |
| 561-805-6672 |
| |
| |