Plan Review Notes
Plan Review Notes For Permit 06050874
Permit Number 06050874
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 3RD REVIEW, FROM PREVIOUS LIST:
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE
 PLAN.DESIGN PRESSURES FOR BUILDINGS
 OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 2ND REVIEW - PAPERWORK SUBMITTED SHOWS A
 MEAN ROOF HEIGHT OF 120'.
  
 3RD REVIEW - ENGINEERING REQUIRED.
  
 _XX_4.ANCHORING NOT COMPLIANT FOR
 THE DESIGN PRESSURES YOU HAVE DECLARED.
  
 3RD REVIEW - YOU HAVE CIRCLED ANCHORING
 FOR -60PSF, THE COMPUTERIZED ENGINEERING
 SPECIFIES -108.6.
  
 DESIGN PRESSURES FOR BUILDINGS OVER 60'
 MUST BE SPECIFIED BY AN ENGINEER.TWO
 SIGNED, SEALED, DATED ORIGINALS
 REQUIRED.YOU CANNOT USE A COMPUTER
 PROGRAM TO DETERMINE DESIGN PRESSURES
 FOR BUILDINGS OVER 60' UNLESS IT IS
 SEALED BY AN ENGINEER.
  