Date |
Text |
2006-08-16 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2004 |
| |
| 3RD REVIEW, FROM PREVIOUS LIST: |
| |
| _XX_2.PROVIDE BUILDING HEIGHT ON THE |
| PLAN.DESIGN PRESSURES FOR BUILDINGS |
| OVER 60FEET ARE REQUIRED TO BE DESIGNED |
| USING ASCE7, FBC1609.1.1 AND MUST BE |
| DONE BY AN ENGINEER. DOCUMENTS PREPARED |
| BY AN ENGINEER AND SUBMITTED FOR PUBLIC |
| RECORD ARE TO BE SIGNED SEALED ORIGINALS |
| FAC61G15-23.002. |
| |
| 2ND REVIEW - PAPERWORK SUBMITTED SHOWS A |
| MEAN ROOF HEIGHT OF 120'. |
| |
| 3RD REVIEW - ENGINEERING REQUIRED. |
| |
| _XX_4.ANCHORING NOT COMPLIANT FOR |
| THE DESIGN PRESSURES YOU HAVE DECLARED. |
| |
| 3RD REVIEW - YOU HAVE CIRCLED ANCHORING |
| FOR -60PSF, THE COMPUTERIZED ENGINEERING |
| SPECIFIES -108.6. |
| |
| DESIGN PRESSURES FOR BUILDINGS OVER 60' |
| MUST BE SPECIFIED BY AN ENGINEER.TWO |
| SIGNED, SEALED, DATED ORIGINALS |
| REQUIRED.YOU CANNOT USE A COMPUTER |
| PROGRAM TO DETERMINE DESIGN PRESSURES |
| FOR BUILDINGS OVER 60' UNLESS IT IS |
| SEALED BY AN ENGINEER. |
| |