2006-07-07 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 2ND REVIEW, FROM PREVIOUS LIST:
  
  
  
 _XX_2.PROVIDE BUILDING HEIGHT ON THE
 PLAN.DESIGN PRESSURES FOR BUILDINGS
 OVER 60FEET ARE REQUIRED TO BE DESIGNED
 USING ASCE7, FBC1609.1.1 AND MUST BE
 DONE BY AN ENGINEER. DOCUMENTS PREPARED
 BY AN ENGINEER AND SUBMITTED FOR PUBLIC
 RECORD ARE TO BE SIGNED SEALED ORIGINALS
 FAC61G15-23.002.
  
 2ND REVIEW - PAPERWORK SUBMITTED SHOWS A
 MEAN ROOF HEIGHT OF 120'.
  
 NEW COMMENT:
  
 _XX_3.PROVIDE A COPY OF THE CONDO
 ASSOCIATION APPROVAL.
  
 _XX_4.ANCHORING NOT COMPLIANT FOR
 THE DESIGN PRESSURES YOU HAVE DECLARED.
  
  