Plan Review Notes For Permit 06050873 |
Permit Number |
06050873 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-06-08 00:00:00 | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | INGS REQUIRED PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. | | MINIMUM 3,750 CUBIC FEET REQUIRED. |
|