Plan Review Notes
Plan Review Notes For Permit 06050845
Permit Number 06050845
Review Stop M
Sequence Number 8
Notes
Date Text
2008-05-27 14:39:34PG M-2 REVISION 5
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 COMMENTS:
  
 1. IN THIS REVISION, RETURN AIR HAS BEEN REMOVED AN
 OFFICE IN QUADRANT 2A. BALANCED RETURN IS REQUIRED IN
 THIS AREA IN ACCORDANCE WITH FBCM 601.4. SHOW HOW
 BALANCED AIR IS TO BE ACHIEVED.
  
 2. THE SUPPLY BRANCH FEEDING VAV 05 IN THE SAME OFFICE
 IS MISSING SIZE ON THE PLANS. PLEASE PROVIDE MISSING
 INFORMATION ON PLANS. FBCM 603.1 AND FBCB 106.1.1.
  
 NOTE: PREVIOUS REVISION 5 ON PAGE M-3 WAS REVIEWED WITH
 A PROVISO REGARDING AN OFFICE WHICH WAS MISSING A
 RETURN. PLEASE ADDRESS THE PROVISO ON M-3 WHEN
 RESUBMITTING PAGE M-2. WORK SHALL BE INSTALLED IN
 ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS,
 AND ANY CHANGES MADE DURING CONSTRUCTION THAT ARE NOT
 IN COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS
 SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF
 CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH FBCM 106.4.
  