Plan Review Notes For Permit 06050845 |
Permit Number |
06050845 |
|
Review Stop |
M |
Sequence Number |
8 |
|
Notes |
Date |
Text |
2008-05-27 14:39:34 | PG M-2 REVISION 5 | | ACTION: DENIED | | | | FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | COMMENTS: | | | | 1. IN THIS REVISION, RETURN AIR HAS BEEN REMOVED AN | | OFFICE IN QUADRANT 2A. BALANCED RETURN IS REQUIRED IN | | THIS AREA IN ACCORDANCE WITH FBCM 601.4. SHOW HOW | | BALANCED AIR IS TO BE ACHIEVED. | | | | 2. THE SUPPLY BRANCH FEEDING VAV 05 IN THE SAME OFFICE | | IS MISSING SIZE ON THE PLANS. PLEASE PROVIDE MISSING | | INFORMATION ON PLANS. FBCM 603.1 AND FBCB 106.1.1. | | | | NOTE: PREVIOUS REVISION 5 ON PAGE M-3 WAS REVIEWED WITH | | A PROVISO REGARDING AN OFFICE WHICH WAS MISSING A | | RETURN. PLEASE ADDRESS THE PROVISO ON M-3 WHEN | | RESUBMITTING PAGE M-2. WORK SHALL BE INSTALLED IN | | ACCORDANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS, | | AND ANY CHANGES MADE DURING CONSTRUCTION THAT ARE NOT | | IN COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS | | SHALL BE RESUBMITTED FOR APPROVAL AS AN AMENDED SET OF | | CONSTRUCTION DOCUMENTS IN ACCORDANCE WITH FBCM 106.4. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|