Plan Review Notes
Plan Review Notes For Permit 06050845
Permit Number 06050845
Review Stop M
Sequence Number 3
Notes
Date Text
2006-09-28 00:00:00----------------DENIED------------------
 1. PAGE M2 QUADRANT 2B: MISSING FIRE
 DAMPER ON 8" ROUND DUCT FROM TO 05 VAV
 IN 'RECEPTION' TO 'OFFICE' 250 CFM DROP.
  
 2. PAGE M10 DETAIL #2: PLEASE INDICATE
 OF WHAT MATERIAL THE ROOF DUCT STANDS
 ARE TO BE CONSTRUCTED, AS WELL AS DETAIL
 FOR FASTENING STANDS TO ROOF IN ORDER TO
 MEET WIND-LOAD REQUIREMENTS.
  
 3. PAGE M10 DETAIL #1B: ALL UL 155
 LISTED FIRE DAMPERS MUST BE INSTALLED
 ACCORDING TO MANUFACTURER'S INSTALLATION
 INSTRUCTIONS. PROVIDE THEM EITHER ON THE
 PLAN OR SEPERATELY.
  