Plan Review Notes For Permit 06050845 |
Permit Number |
06050845 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-09-28 00:00:00 | ----------------DENIED------------------ | | 1. PAGE M2 QUADRANT 2B: MISSING FIRE | | DAMPER ON 8" ROUND DUCT FROM TO 05 VAV | | IN 'RECEPTION' TO 'OFFICE' 250 CFM DROP. | | | | 2. PAGE M10 DETAIL #2: PLEASE INDICATE | | OF WHAT MATERIAL THE ROOF DUCT STANDS | | ARE TO BE CONSTRUCTED, AS WELL AS DETAIL | | FOR FASTENING STANDS TO ROOF IN ORDER TO | | MEET WIND-LOAD REQUIREMENTS. | | | | 3. PAGE M10 DETAIL #1B: ALL UL 155 | | LISTED FIRE DAMPERS MUST BE INSTALLED | | ACCORDING TO MANUFACTURER'S INSTALLATION | | INSTRUCTIONS. PROVIDE THEM EITHER ON THE | | PLAN OR SEPERATELY. | | | | RONALD J REGUEIRO | | 561.805.6734 | | [email protected] |
|