Plan Review Notes
Plan Review Notes For Permit 06050845
Permit Number 06050845
Review Stop M
Sequence Number 2
Notes
Date Text
2006-08-18 00:00:00*** DENIED ***
 1) SEE PAGE M-2 NEED FIRE DAMPERS AT 5"
 AND 4" DUCTS TO OFFICE, SEE HIGH LIGHT
 (JURY ROOM ON ELECT. PG. E-3).
  
 2) SEE PAGE M-4 MANY DUCTS AND GRILLS
 ARE NOT SIZED, SEE HIGH LIGHT.
  
 3) SEE PAGE S-1 WIND LOAD FBC 2001, WE
 ARE PRESENTLY USING 2004 FBC, PLEASE
 CORRECT.
  
 5) SHOW ON MECHANICAL PLANS LOCATION OF
 CONDENSATE LINES AND WERE THEY WILL
 TERMINATE.
  
 6) PLEASE SUBMIT ENERGY CALCULATIONS,
 PER 2004 FBC/EB 611.1 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.