Plan Review Notes For Permit 06050845 |
Permit Number |
06050845 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-08-18 00:00:00 | *** DENIED *** | | 1) SEE PAGE M-2 NEED FIRE DAMPERS AT 5" | | AND 4" DUCTS TO OFFICE, SEE HIGH LIGHT | | (JURY ROOM ON ELECT. PG. E-3). | | | | 2) SEE PAGE M-4 MANY DUCTS AND GRILLS | | ARE NOT SIZED, SEE HIGH LIGHT. | | | | 3) SEE PAGE S-1 WIND LOAD FBC 2001, WE | | ARE PRESENTLY USING 2004 FBC, PLEASE | | CORRECT. | | | | 5) SHOW ON MECHANICAL PLANS LOCATION OF | | CONDENSATE LINES AND WERE THEY WILL | | TERMINATE. | | | | 6) PLEASE SUBMIT ENERGY CALCULATIONS, | | PER 2004 FBC/EB 611.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|