Plan Review Notes For Permit 06050845 |
Permit Number |
06050845 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-19 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2. EXITS SHALL NOT BE BLOCKED BY | | CONSTRUCTION DEBRIS AND THEY SHALL | | REMAIN PASSABLE AT ALL TIMES. | | | | 3. INTERIOR FINISH ON WALLS AND CEILINGS | | IN EXIT ACCESS AND EXIT AREAS SHALL BE | | CLASS A. | | | | 4. ALL NEW ELECTRICAL WORK TO COMPLY | | WITH NFPA 70, THE NATIONAL ELECTRICAL | | CODE. | | | | 5. THE NEW DUCT SMOKE DETECTORS WHEN | | ACTIVATED SHALL ACTIVATE THE BUILDINGS | | FIRE ALARM SYSTEM. | | | | 6. ALL NEW FIRE DAMPERS AFTER | | INSTALLATION ARE TO BE TESTED TO ENSURE | | PROPER FUNCTION AND OPERATION. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|