Date |
Text |
2006-06-10 00:00:00 | ** UNSAT ** |
| |
| ** PLEASE SEE THIS WAS ORIGINALLY |
| SUBMITTED UNDER THE 2001 FBC AND ONLY AS |
| A "PLAN REVIEW". |
| PLEASE SEEE THIS IS NOW SUBMITTED UNDER |
| THE 2004 FBC. |
| |
| 1) NOTE: PLEASE SEE FBC CHAPTER 13 FOR |
| MIN CALCULATIONS FOR RENOVATIONS TO |
| EXISTING. |
| PLEASE SEE PRESCRIPTIVE REQUIREMENTS |
| AND FORM USE. PLEASE SEE THIS WILL ALSO |
| BE IN THE MECHANICAL REVIEW NOTES. |
| PLEASE SEE 13-413.1.ABC.1 FOR VOLTAGE |
| DROP. |
| PLEASE SEE A WORST CASE VOLTAGE DROP |
| SHALL BE SHOWN ON PLANS. ONE FOR THE |
| FEEDERS AND ONE FOR THE NEW BRANCH |
| CIRCUITS. |
| |
| 2) NOTE: PLEASE SEE THE ONE LINE RISER |
| DIAGRAM WHICH ONLY SHOWS ONE SET OF |
| 500MCM'S TO EACH "AM" AND "BM". |
| PLEASE SEE THIS SEEMS TO BE A MISPRINT |
| AS ONE SETS TO EACH ONLY PROVIDES 400A'S |
| WHEREAS THE MAINS ARE 800A. |
| 310.16,240.4 ETC |
| |
| 3) NOTE: PLEASESHOW OR NOTE THAT THE |
| CONTINUOUS LOADS AND LARGEST MOTOR LOADS |
| ARE ALREADY FIGURED IN THE CALCULATIONS |
| AT 125%. PLEASE REVISE CALCULATIONS TO |
| INCLUDE THIS . |
| 215.3, 230.42 |
| |
| PLEASE REMOVE OLD/VOIDED SHEETS AND ONLY |
| INSERT NEW REVISED SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. |
| ONE COPY OF ANY OF THE OLD REMOVED |
| VOIDED SHEETS SHOULD BE SUBMITTED FOR |
| REFERECNE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |