2006-05-31 00:00:00 | ******DENIED****** | | FEFERENCE: FBC-2004 FUEL GAS | | FBC-2004 CHAPTER 1 | | FLORIDA ADMINISTRATIVE CODE | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR PLAN REVIEW FOR A GAS PERMIT: | | | | 1. ORIGANAL PLANS #04121374 ARE SIGNED | | AND SEALED BY AN ENGINEER. ANY REVISIONS | | TO THE ORIGINAL CONSTRUCTION DOCUMENTS | | BY L&R GAS CONTRACTORS, INC. NEED TO BE | | SIGNED AND SEALED BY THE ENGINEER OF | | RECORD. | | 2. THE MAXITROL REGULATORS INDICATED FOR | | THE WATER HEATER AND THE GENERATOR ARE | | TO SMALL FOR THE INDIVIDUAL LOADS OF THE | | APPLIANCES, SEE ATTACHED MAXITROL SHEETS | | FOR REFERENCE FOR RESUBMITTAL. | | | | END OF COMMENTS: | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | UNDER SUPERVISION OF K.STEVENS | | (561) 805-6721 |
|