Plan Review Notes For Permit 06050839
Permit Number 06050839
Review Stop E
Sequence Number 3
Notes
Date Text
2006-07-20 00:00:00********* UNSAT *************
  
 1) NOTE: PLEASE SEE TWO COMPLETELY
 DIFFERENT SETS AND RISER DIAGRAMS ARE
 SUBMITTED.
 PLEASE SEE ONE SHOWS 30A SERVICE AND THE
 OTHER 60A?
 PLEASE SEE THE 60A SERVICE APPEARS TO BE
 THE ONE MEETING CODE COMPLIANCE FOR USE.
 PLEASE SEE TWO DIFFERENT DESIGN
 PROFESSIONALS FOR EACH EELCTRICAL
 DESIGNS?
 PLEASE KNOW, DUE TO BLDG COMMENTS AND
 NON-COMPLIANCE FOR THE BLDGSHEETS THE
 ELECTRICAL STAMPS WERE CROSSED OUT AND
 VOIDED.
  
 **IMPORTANT**
 PLEASE SUBMIT TWO SETS OF COMPLETE
 PLANS. PLEASE REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW APPROPRIATE
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING.
  
 215.5,240.4,310.16, 408.4. FBC 106.1.2,
  
 2) NOTE: PLEASE SEE BLDG COMMENTS AS
 MISSING THE CERTIFICATE OF AUTHORIZATION
 # ON TITLE BLOCKS FOR ENGINEERING FIRM
 AS REQUIRED.
  
 3) NOTE: PLEASE SEE BOTH SETS OF SURVEYS
 SUBMITTED CONTAIN A "RUBBER STAMP" FOR
 THE REQUIRED ORIGINAL SIGNATURE. PLEASE
 SEE FAC 61G17, FS 472.025
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  