 NONCOMPLIANT
  
 INDICATE WHERE THE SIGN IS FED FROM,
 ALSO THE TWO LIGHTS SHOWN. GIVE
 PANEL/TIME CLOCK LOCATION/DESIGNATION,
 AND CIRCUIT NUMBERS.
  
 THERE IS A RISER DIAGRAM ON THE PLAN
 WHICH INDICATES A SEPARATE SERVICE FOR
 THE SIGN. IF THIS IS THE CASE COMPLETE
 THE RISER WITH GEC PER 250.66, AND OCP
 AND CIRCUIT NUMBERS FOR THE SIGN. LOCATE
 THE SERVICE ON THE SITE PLAN. IF THERE
 IS NO SERVICE IN THIS PROJECT, PLEASE
 REMOVE THE RISER.
  
  