Plan Review Notes For Permit 06050837 |
Permit Number |
06050837 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-08 00:00:00 | | | | | ******PROVISO****** | | 1. LOCAL ORD. #2853-95, BACKFLOW | | REQUIRED ON WATER SERVICE. | | 2.FBC-2004 PLUMBING TABLE 403.1 DRINKING | | FOUNTAIN REQUIRED, PER FBC-2004 PLUMBING | | SECTION 410.1 BOTTLED WATER DISPENSERS | | SHALL BE PERMITTED TO BE SUBSTITUTED FOR | | NOT MORE THAN 50 PERCENT OF THE REQUIRED | | DRINKING FOUNTAINS. | | 3. PER FBC-2004 CHAPTER 11, SECTION | | 11-4.19.3, THE LAVATORY IN BATHROOM 202 | | SHALL HAVE A CLEAR FLOOR SPACE OF 30 | | INCHES BY 48 INCHES. |
|