2006-06-06 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| |
| THE FOLLOWING INFORMATION IS REQUESTED |
| FOR GAS PLAN REVIEW: |
| |
| 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL |
| A GEN/RES PERMIT APPLICATION HAS BEEN |
| APPLIED FOR AND APPROVED BY ZONING FOR |
| THE GENERATOR LOCATION.(NOTE: ZONING |
| FAILED 6/1/06 SEE ATTACHED SHEET FOR |
| REFERENCE) |
| 2. NOTE: MORE INFORMATION REQUIRED, |
| HOUSE HAS EXISTING GAS, PLEASE INDICATE |
| THE FOLLOWING INFORMATION ON THE |
| RESUBMITTED DRAWING. SEE ATTACHED SHEET |
| FOR REFERENCE INDICATING EXISTING GAS |
| PIPING. |
| 3. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE.(NOTE: INDICATE EXISTING |
| PIPE AND NEW PIPE TO GENERATOR ON |
| RESUBMITTED DRAWINGS) |
| 4. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| (NOTE: INDICATE THE ABOVE INFORMATION TO |
| EXISTING PIPING AND TO PROPOSED PIPING |
| TO GENREATOR ON RESUBMITTED DRAWINGS) |
| 5. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33).(NOTE: EXISTING GAS PIPE IS |
| PART OF SYSTEM PLEASE INCLUDE TOTAL BTU |
| LOAD OF SYSTEM ON RESUBMITTED DRAWINGS) |
| 6. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4).(NOTE: |
| EXISTING GAS PIPE IS PART OF SYSTEM, |
| LONGEST LENGTH METHOD OF SYSTEM TO BE |
| USED FOR SIZING PLEASE INDICATE THE |
| ABOVE INFORMATION ON THE RESUBMITTED |
| DRAWINGS) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |