Plan Review Notes For Permit 06050792 |
Permit Number |
06050792 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-01 00:00:00 | | | | | DENIED | | | | 1) A DESIGN PROFESSIONAL THAT IS | | REGISTERED TO PRACTICE UNDER CHAPTER 481 | | OR 471 OF THE FLORIDA STATUTES SHALL | | AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND | | DATE TO SAID DRAWINGS AND SPECIFICATIONS | | PER 106.1 FBC 2004 | | | | 2) WINDOW MANUFACTURERS ALL HAVE | | DIFFERENT SIZES ATTACHED TO THEIR WINDOW | | DESIGNATIONS (34SH, 35SH ETC.) PLEASE | | PROVIDE ACTUAL WINDOW SIZE THAT WILL BE | | USED | | | | 3) SEVERAL WINDOWS ARE MULLED TOGETHER, | | PROVIDE PRODUCT APPROVALS FOR THE WINDOW | | MULLIONS | | | | 4) PROVIDE THE TYPE OF CONSTRUCTION OF | | THE BUILDING ( WOOD FRAME, BLOCK ETC.) | | | | 5) WHERE OVER 25% OF THE TOTAL GLAZED | | AREA OF THE BUILDING IS REPLACED IN A 12 | | MONTH PERIOD THE OPENINGS ARE REQUIRED | | TO BE IMPACT PROTECTED. AS THESE WINDOWS | | ARE NON-IMPACT RATED SHUTTERS WILL BE | | REQUIRED. PROVIDE PRODUCT APPROVALS FOR | | SHUTTERS OR PROOF OF EXISTING SHUTTERS | | ( COPY OF PERMIT OR NOTORIZED LETTER) | | | | A RECORDED COPY OF THE NOTICE OF | | COMMENCEMENT IS REQUIRED PRIOR TO | | A PERMIT BEING ISSUED | | | | | | BLDG PLAN REVIEW | | ADRIAN MORSE | | 561-805-6716 | | | | | | | | | | | | | | | | | | | | |
|