Plan Review Notes
Plan Review Notes For Permit 06050791
Permit Number 06050791
Review Stop M
Sequence Number 1
Notes
Date Text
2006-05-22 00:00:00*** DENIED ***
 1) THE ENGINEER'S SEAL AND SIGNATURE
 MUST BE ON PLANS THAT HAVE HIS NAME IN
 THE TITLE BLOCK, PER FAC61G15-23.002 .
  
 2) A/C DUCT LAY-OUT ON MECHANICAL PLANS
 CAN NOT BE DONE IN PENCIL.
  
 3) PLEASE SHOW THE SIZE OF THE RETURN
 AIR TRANSFER GRILLS OVER THE BEDROOM
 DOORS.
  
 4) PLEASE SHOW CONDENSATE DRAIN LINE
 LOCATION ON PLANS.
  
 5) SHOW DUCT SIZE FROM AHU TO MIXING
 BOX.
  
 6) PLEASE SHOW GRILL SIZE AND CFM'S. FOR
 DINING ROOM AND KITCHEN.
  
 7) PLEASE SUBMIT A PROROSAL FOR JOB WITH
 PRICE AND CUSTOMERS SIGNATURE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  