2006-08-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)PROVIDE ANCHOR SPACING, EITHER BY
 CIRCLING IT ON THE PRODUCT APPROVAL OR
 BY INCLUDING IT ON THE INSTALLATION
 SCHEDULE.
  
 2ND REVIEW - MULTIPLE NUMBERS WERE
 CIRCLED ON THE PRODUCT APPROVAL.ONLY
 ONE OPENING, HOW CAN YOU HAVE DIFFERENT
 ANCHOR SPACING?
  
 THE OPENING SCHEDULE PROVIDES 130" AS
 THE HEIGHT, ID SCHEDULE IS 120".
  
 2.)REMOVABLE SHUTTERS ON COMMERCIAL
 BUILDINGS MUST BE APPROVED BY THE
 BUILDING OFFICIAL.SEE ATTACHED, ITEM
 #13.SUBMIT A PLAN WITH ALL REQUIRED
 INFORMATION.
  
 THIS PLAN MAY BE SUBMITTED BY EMAIL.A
 FLOOR PLAN SHOWING WHERE THE SHUTTERS
 WILL BE STORED WILL BE REQUIRED AS PART
 OF THE PLAN.THE PLAN SHOULD BE
 SUBMITTED PRIOR TO RESUBMITTAL OF THE
 PERMIT APPLICATION.AFTER A PRELIMINARY
 REVIEW, AN ORIGINAL SIGNED BY THE OWNER
 WILL BE REQUIRED.
  
 2ND REVIEW - PLAN SUBMITTED, BUT PLESE
 REVISE THE FOLLOWING:
  
 A.THE PLAN REFERS TO AN ATTACHMENT FOR
 STORAGE LOCATION,NOTHING ATTACHED.THE
 PLAN SHOULD PROVIDE THE SIZE OF THE AREA
 WHERE THE SHUTTERS WILL BE STORED AS
 WELL AS SPECIFICALLY WHERE THEY WILL BE
 STORED WITHIN THAT AREA, WITH
 DIMENSIONS.
  
 B.PLAN DOES NOT INDICATE WHO BRUCE LE
 IS. RESPONSIBLE PARTY IS TO BE LOCATED
 IN PALM BEACH COUNTY; THIS WAS NOT
 ADDRESSED.
  
 C.THE PLAN DID NOT PROVIDE A
 COMMITMENT AS TO WHEN THE SHUTTERS WILL
 BE INSTALLED.
  
 D.SHOW PROXIMITY OF SHUTTER STORAGE
 LOCATION RELATIVE TO THE OPENING.
  
 E.A LADDER WILL BE REQUIRED FOR THIS
 INSTALLATION.ADDRESS THIS IN THE PLAN;
 SHOW WHERE THE LADDER WILL BE STORED.
  