2006-08-16 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS |
| TO THE FBC2004 |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)PROVIDE ANCHOR SPACING, EITHER BY |
| CIRCLING IT ON THE PRODUCT APPROVAL OR |
| BY INCLUDING IT ON THE INSTALLATION |
| SCHEDULE. |
| |
| 2ND REVIEW - MULTIPLE NUMBERS WERE |
| CIRCLED ON THE PRODUCT APPROVAL.ONLY |
| ONE OPENING, HOW CAN YOU HAVE DIFFERENT |
| ANCHOR SPACING? |
| |
| THE OPENING SCHEDULE PROVIDES 130" AS |
| THE HEIGHT, ID SCHEDULE IS 120". |
| |
| 2.)REMOVABLE SHUTTERS ON COMMERCIAL |
| BUILDINGS MUST BE APPROVED BY THE |
| BUILDING OFFICIAL.SEE ATTACHED, ITEM |
| #13.SUBMIT A PLAN WITH ALL REQUIRED |
| INFORMATION. |
| |
| THIS PLAN MAY BE SUBMITTED BY EMAIL.A |
| FLOOR PLAN SHOWING WHERE THE SHUTTERS |
| WILL BE STORED WILL BE REQUIRED AS PART |
| OF THE PLAN.THE PLAN SHOULD BE |
| SUBMITTED PRIOR TO RESUBMITTAL OF THE |
| PERMIT APPLICATION.AFTER A PRELIMINARY |
| REVIEW, AN ORIGINAL SIGNED BY THE OWNER |
| WILL BE REQUIRED. |
| |
| 2ND REVIEW - PLAN SUBMITTED, BUT PLESE |
| REVISE THE FOLLOWING: |
| |
| A.THE PLAN REFERS TO AN ATTACHMENT FOR |
| STORAGE LOCATION,NOTHING ATTACHED.THE |
| PLAN SHOULD PROVIDE THE SIZE OF THE AREA |
| WHERE THE SHUTTERS WILL BE STORED AS |
| WELL AS SPECIFICALLY WHERE THEY WILL BE |
| STORED WITHIN THAT AREA, WITH |
| DIMENSIONS. |
| |
| B.PLAN DOES NOT INDICATE WHO BRUCE LE |
| IS. RESPONSIBLE PARTY IS TO BE LOCATED |
| IN PALM BEACH COUNTY; THIS WAS NOT |
| ADDRESSED. |
| |
| C.THE PLAN DID NOT PROVIDE A |
| COMMITMENT AS TO WHEN THE SHUTTERS WILL |
| BE INSTALLED. |
| |
| D.SHOW PROXIMITY OF SHUTTER STORAGE |
| LOCATION RELATIVE TO THE OPENING. |
| |
| E.A LADDER WILL BE REQUIRED FOR THIS |
| INSTALLATION.ADDRESS THIS IN THE PLAN; |
| SHOW WHERE THE LADDER WILL BE STORED. |
| |