Plan Review Notes
Plan Review Notes For Permit 06050754
Permit Number 06050754
Review Stop P
Sequence Number 1
Notes
Date Text
2006-06-06 00:00:00******DENIED******
 REFERENCE: FBC-2004 SEC. 424.2 OR
 FBC-2004 RESIDENTIAL SEC R4101
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) AS OF 10/1/05 FBC-2004 CODES WENT
 INTO EFFECT PLEASE CORRECTDRAWINGS TO
 REFLECT THE NEW CODE CHANGES FOR
 RESUBMITTAL.
 2) COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS.(PLEASE ADD TO NOTES FOR
 RESUBMITTAL)
 3) FBC-2004 424.2.6.6.2, OR FBCR-2004
 SEC R4101.6.6.2 SHOW COMPLIANCE WITH
 ANSI/ASME A112.19.8M. PROVIDE MODEL
 NUMBER AND MANUF INFO FOR VAC LOCK.
 (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES)
 4) FBC-2004 SEC. 424.2.7.2, OR FBCR-2004
 SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL
 BE MOUNTED ON A SUBSTANTIAL BASE IN A
 MANNER THAT WILL ELIMINATE STRAIN ON
 PIPING.SLAB SHALL BE A NOMINAL 4"
 THICK. (DETAIL REQUIRED)
 5) FBC-2004 SEC. 424.2.13.2, OR
 FBCR-2004 SEC.R4101.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21,(ADD
 TO NOTES)
 6) PLEASE ADD HEATER TO PIPING SCHEMATIC
 FOR RESUBMITTAL.
 7) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 8) FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
 9) FBC-2004 SEC. 424.2.14.4, OR
 FBCR-2004 SEC. R4101.14.4 CONNECTIONS,
 ALL WATER HEATING EQUIPMENT SHALL BE
 INSTALLED WITH FLANGES OR UNION
 CONNECTIONS ADJACENT TO THE HEATER.
 (ADD TO NOTES)
 10) FBC-2004 SEC. 424.2.14, OR FBCR-2004
 SEC. R4101.15 GAS PIPING SHALL COMPLY
 WITH FBC FUEL GAS.SEPARATE PLANS AND
 PERMIT REQUIRED.(ADD TO NOTES)
 11) FBC-2004 SEC. 13-612.1.ABC.2.3.3
 TIME CLOCKS SHALL BE INSTALLED ON
 PRIVATE POOLS.( PLEASE ADD TO DRAWING)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  