2006-06-06 00:00:00 | ******DENIED****** |
| REFERENCE: FBC-2004 SEC. 424.2 OR |
| FBC-2004 RESIDENTIAL SEC R4101 |
| |
| PLEASE ADJUST YOUR NOTES, DETAILS, OR |
| SUBMITTALS TO REFLECT THE FOLLOWING |
| INFORMATION REQUIRED FOR PLAN REVIEW: |
| |
| 1) AS OF 10/1/05 FBC-2004 CODES WENT |
| INTO EFFECT PLEASE CORRECTDRAWINGS TO |
| REFLECT THE NEW CODE CHANGES FOR |
| RESUBMITTAL. |
| 2) COMPLY WITH FBC-2004 SEC 424.2, OR |
| FBCR-2004 SEC R4101 PRIVATE SWIMMING |
| POOLS.(PLEASE ADD TO NOTES FOR |
| RESUBMITTAL) |
| 3) FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| ANSI/ASME A112.19.8M. PROVIDE MODEL |
| NUMBER AND MANUF INFO FOR VAC LOCK. |
| (GIVE DETAIL, SUBMITTAL OR ADD TO NOTES) |
| 4) FBC-2004 SEC. 424.2.7.2, OR FBCR-2004 |
| SEC. R4101.7.2 PUMPS AND EQUIPMENT SHALL |
| BE MOUNTED ON A SUBSTANTIAL BASE IN A |
| MANNER THAT WILL ELIMINATE STRAIN ON |
| PIPING.SLAB SHALL BE A NOMINAL 4" |
| THICK. (DETAIL REQUIRED) |
| 5) FBC-2004 SEC. 424.2.13.2, OR |
| FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| CONNECTIONS, FBC PLMG SEC 605.21,(ADD |
| TO NOTES) |
| 6) PLEASE ADD HEATER TO PIPING SCHEMATIC |
| FOR RESUBMITTAL. |
| 7) FBC-2004 SEC. 424.2.14.1, OR |
| FBCR-2004 SEC. R4101.14.1 SWIMMING POOL |
| WATER HEATERS SHALL BEAR THE LABEL OF A |
| RECOGNIZED TESTING AGENCY. (MANUFACTURE |
| SHEETS REQUIRED, PLEASE SUBMIT) |
| 8) FBC-2004 SEC. 424.2.14.2, OR |
| FBCR-2004 SEC. R4101.14.2 WATER |
| RETENTION, PROVIDE A POSITIVE MEANS OF |
| RETAINING WATER IN THE HEATER WHEN PUMP |
| IS SHUT OFF.(MANUFACTURE SHEETS |
| REQUIRED, PLEASE SUBMIT) |
| 9) FBC-2004 SEC. 424.2.14.4, OR |
| FBCR-2004 SEC. R4101.14.4 CONNECTIONS, |
| ALL WATER HEATING EQUIPMENT SHALL BE |
| INSTALLED WITH FLANGES OR UNION |
| CONNECTIONS ADJACENT TO THE HEATER. |
| (ADD TO NOTES) |
| 10) FBC-2004 SEC. 424.2.14, OR FBCR-2004 |
| SEC. R4101.15 GAS PIPING SHALL COMPLY |
| WITH FBC FUEL GAS.SEPARATE PLANS AND |
| PERMIT REQUIRED.(ADD TO NOTES) |
| 11) FBC-2004 SEC. 13-612.1.ABC.2.3.3 |
| TIME CLOCKS SHALL BE INSTALLED ON |
| PRIVATE POOLS.( PLEASE ADD TO DRAWING) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |