Date |
Text |
2006-06-28 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)ADDRESSED. |
| |
| 2.)FLORIDA STATE OR LOCAL PRODUCT |
| APPROVAL REQUIRED, FAC9B72.THE STATE |
| PRODUCT APPROVAL IS EXPIRED (2001 CODE |
| RATHER THAN FBC2004). |
| |
| (3RD REVIEW) SEE FAC9B72.AN |
| APPLICATION IS REQUIRED.ALL |
| ENGINEERING IS TO BE SIGNED, SEALED, |
| DATED ORIGINALS. |
| |
| 3.)THE NOA STATES THAT THE PRODUCT |
| SPECIFIED IS FOR USE OVER STEEL FRAMING. |
| THE CBAA PAPERWORK INDICATES THAT THIS |
| IS OVER WOOD FRAMING.ENGINEERING, WITH |
| LOCAL PRODUCT APPROVAL APPLICATION, IS |
| REQUIRED. |
| |
| NOT ADDRESSED.PLEASE SUBMIT LOCAL |
| PRODUCT APPROVAL APPLICATION FAC9B72, |
| WWW.FLORIDABUILDING.ORG. |
| |
| ALSO SUBMIT LEGIBLE MIAMI-DADE NOAS. |
| THE NOAS SUBMITTED ARE DIFFICULT TO |
| READ. |
| |
| 4.) ADDRESSED. |
| |
| 5.)THE CBAA CASE AND PAPERWORK |
| INCLUDED REFER TO WORK WHICH IS NOT |
| WITHIN THE SCOPE OF A CCC LICENSE: FIRE |
| SPRINKLERS, FIREPROOFING OF STRUCTURAL |
| ELEMENTS, REPAIR OF WOOD FRAMING.THE |
| PLANS WHICH YOU WILL SUBMIT SHOULD MAKE |
| CLEAR THE SCOPE OF WORK UNDER THIS |
| PERMIT APPLICATION.PROVIDE APPLICATION |
| NUMBERS OF THE OTHER WORK ASSOCIATED |
| WITH THIS PROJECT, OR APPLY UNDER A |
| CONTRACTOR LICENSED TO OVERSEE ALL WORK |
| REQUIRED. |
| |
| AS DISCUSSED, HAVE A GENERAL CONTRACTOR |
| (OR OTHER CONTRACTOR LICENSED TO PERFORM |
| THE WORK) APPLY. AS DISCUSSED, THIS CAN |
| BE DONE WITH A CHANGE OF CONTRACTOR. |
| THE ROOFING CONTRACTOR WILL APPLY AS A |
| SUBCONTRACTOR. |
| |
| 3RD REVIEW - NOT ADDRESSED. |
| |
| |
| 8.)IS THERE A WOOD DECK IN ADDITION TO |
| THE WOOD FRAMING?EXISTING CONDITIONS |
| ARE NOT CLEAR. |
| |
| CBAA ORDER REFERS TO WOOD FRAMING.THIS |
| IS NOT SHOWN ON THE ENGINEER'S PLAN. |
| PROVIDE FRAMING INFORMATION (MATERIAL |
| AND SPACING) SO THAT CODE COMPLIANCE CAN |
| BE DETERMINED. |
| |
| 9.)PROVIDE WIND DESIGN CRITERIA |
| FBC1603.1.4, INCLUDING DESIGN PRESSURES |
| FOR THE ROOF. |
| |
| 10.) ON THE APPLICATION, CONTRACTOR |
| STATES THAT THE ROOF PITCH IS 1/12.THE |
| DRAWINGS SHOW 2 1/2/12.CLARIFY THE |
| DISCREPANCY.DESIGN PRESSURES ARE |
| DIFFER FOR THE TWO DIFFERENT CONDITIONS. |
| |
| 11.)THE 60 MINUTE FIRE SPEC TEST WAS |
| OVER DOUGLAS FIR PLYWOOD; THE ENGINEER'S |
| DRAWING SHOWS THE PRODUCT OVER |
| INSULATION.THIS DOES NOT APPEAR TO |
| PROVIDE THE 1 HOUR PROTECTION REQUIRED |
| BY THE CBAA ORDER. |
| |
| NOT ADDRESSED. |
| |
| 12.)THE NOC IS FOR REROOF ONLY.A NEW |
| NOC WILL BE REQUIRED. |
| |
| 13.)PROVIDE PRODUCT APPROVAL FOR THE |
| TU PLUS SHOWN ON THE ENGINEER'S DRAWING |
| (METAL UNDERLAYMENT). |
| |
| NOT ADDRESSED.PRODUCT APPROVALS TO BE |
| REVIEWED BY DESIGNER OF RECORD. |
| |
| 14.)IT IS NOT CLEAR HOW DETAIL A, 1/2, |
| FLASHING AT WALL, WILL KEEP WATER FROM |
| GETTING UNDER WHAT THE PLAN CALLS |
| "PHILADELPHIA FLASHING", FBC1503.2. |
| |
| *********************** |
| 7/13/06 |
| AS THE ROOF IS LEAKING, TO ASSIST IN |
| GETTING THE ROOF PERMIT ISSUED, THE |
| FOLLOWING IS ACCEPTABLE: |
| |
| CHANGE OF CONTRACTOR FOR 06050695 (FROM |
| CCC TO A CGC OR CBC OR OTHER CONTRACTOR |
| LICENSED TO PERFORM OR OVERSEE THE SCOPE |
| OF WORK) |
| |
| ROOFING CONTRACTOR TO APPLY FOR ROOF |
| PERMIT, REFERRING TO 06050695 AS MASTER |
| PERMIT NUMBER |
| |
| LOCAL PRODUCT APPROVAL MAY BE SUBMITTED |
| SEPARATELY FROM THE RESUB FOR 06050695 |
| |