2006-06-13 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 1.)ADDRESSED.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL REQUIRED, FAC9B72.THE STATE
 PRODUCT APPROVAL IS EXPIRED (2001 CODE
 RATHER THAN FBC2004).
  
 NOT ADDRESSED.SEE COMMENT 3 BELOW.
 LOCAL PRODUCT APPROVAL REQUIRED.
  
 3.)THE NOA STATES THAT THE PRODUCT
 SPECIFIED IS FOR USE OVER STEEL FRAMING.
 THE CBAA PAPERWORK INDICATES THAT THIS
 IS OVER WOOD FRAMING.ENGINEERING, WITH
 LOCAL PRODUCT APPROVAL APPLICATION, IS
 REQUIRED.
  
 NOT ADDRESSED.PLEASE SUBMIT LOCAL
 PRODUCT APPROVAL APPLICATION FAC9B72,
 WWW.FLORIDABUILDING.ORG.
  
 ALSO SUBMIT LEGIBLE MIAMI-DADE NOAS.
 THE NOAS SUBMITTED ARE DIFFICULT TO
 READ.
  
 4.) ADDRESSED.
  
 5.)THE CBAA CASE AND PAPERWORK
 INCLUDED REFER TO WORK WHICH IS NOT
 WITHIN THE SCOPE OF A CCC LICENSE: FIRE
 SPRINKLERS, FIREPROOFING OF STRUCTURAL
 ELEMENTS, REPAIR OF WOOD FRAMING.THE
 PLANS WHICH YOU WILL SUBMIT SHOULD MAKE
 CLEAR THE SCOPE OF WORK UNDER THIS
 PERMIT APPLICATION.PROVIDE APPLICATION
 NUMBERS OF THE OTHER WORK ASSOCIATED
 WITH THIS PROJECT, OR APPLY UNDER A
 CONTRACTOR LICENSED TO OVERSEE ALL WORK
 REQUIRED.
  
 AS DISCUSSED, HAVE A GENERAL CONTRACTOR
 (OR OTHER CONTRACTOR LICENSED TO PERFORM
 THE WORK) APPLY. AS DISCUSSED, THIS CAN
 BE DONE WITH A CHANGE OF CONTRACTOR.
 THE ROOFING CONTRACTOR WILL APPLY AS A
 SUBCONTRACTOR.
  
 6.)AS NO PLANS WERE SUBMITTED, CODE
 COMPLIANCE CANNOT BE DETERMINED.BASED
 ON THE FORMULA ON THE PRODUCT APPROVAL,
 THIS PRODUCT DOES NOT MEET THE DESIGN
 PRESSURE LIMITATION FOR ZONES 2 AND 3
 FOR A ROOF 0- 10 DEGREES.
  
 NOT PROPERLY ADDRESSED.DESIGN
 PRESSURES WERE NOT PROVIDED BY THE
 ENGINEER, AND CONFLICTING INFORMATION
 PROVIDED IN REGARDS TO THE ROOF PITCH.
  
 DESIGN PRESSURE LIMITATIONS FOR THE
 PRODUCT ARE NOT CLEAR.THE PRODUCT
 CONTAINS A FORMULA TO DETERMINE UPLIFT
 DP.ACCORDING TO THE FORMULA, DP IS
 -35.37, NOT COMPLIANT FOR COMPONENTS &
 CLADDING.I HAVE LEFT A MESSAGE WITH
 THE MANUFACTURER FOR CLARIFICATION.
  
 7.)DESIGNER OF RECORD IS TO REVIEW THE
 PRODUCT APPROVALS, FBC*106.3.3.
  
 8.)IS THERE A WOOD DECK IN ADDITION TO
 THE WOOD FRAMING?EXISTING CONDITIONS
 ARE NOT CLEAR.
  
 CBAA ORDER REFERS TO WOOD FRAMING.THIS
 IS NOT SHOWN ON THE ENGINEER'S PLAN.
 PROVIDE FRAMING INFORMATION (MATERIAL
 AND SPACING) SO THAT CODE COMPLIANCE CAN
 BE DETERMINED.
  
 NEW COMMENTS:
  
 9.)PROVIDE WIND DESIGN CRITERIA
 FBC1603.1.4, INCLUDING DESIGN PRESSURES
 FOR THE ROOF.
  
 10.) ON THE APPLICATION, CONTRACTOR
 STATES THAT THE ROOF PITCH IS 1/12.THE
 DRAWINGS SHOW 2 1/2/12.CLARIFY THE
 DISCREPANCY.DESIGN PRESSURES ARE
 DIFFER FOR THE TWO DIFFERENT CONDITIONS.
  
 11.)THE 60 MINUTE FIRE SPEC TEST WAS
 OVER DOUGLAS FIR PLYWOOD; THE ENGINEER'S
 DRAWING SHOWS THE PRODUCT OVER
 INSULATION.THIS DOES NOT APPEAR TO
 PROVIDE THE 1 HOUR PROTECTION REQUIRED
 BY THE CBAA ORDER.
  
 12.)THE NOC IS FOR REROOF ONLY.A NEW
 NOC WILL BE REQUIRED.
  
 13.)PROVIDE PRODUCT APPROVAL FOR THE
 TU PLUS SHOWN ON THE ENGINEER'S DRAWING
 (METAL UNDERLAYMENT).
  
 14.)IT IS NOT CLEAR HOW DETAIL A, 1/2,
 FLASHING AT WALL, WILL KEEP WATER FROM
 GETTING UNDER WHAT THE PLAN CALLS
 "PHILADELPHIA FLASHING", FBC1503.2.