Plan Review Notes For Permit 06050695 |
Permit Number |
06050695 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-21 00:00:00 | ***DENIED*** | | | | 1) CONTRACT PROPOSAL INDICATES A TOTAL | | OF (24) FIRE SPRINKLER RELOCATIONS | | WITHIN THE SCOPE OF THIS PROJECT. | | SEPARATE SHOP DRAWINGS AND PERMIT IS | | REQUIRED. A (2) HOUR PRESSURE TEST SHALL | | BE DONE UNLESS THE SPRINKLER SYSTEM | | CAN'T BE ISOLATED. IF THAT CONDITION | | EXISTS, A LETTER STATING THIS WITH THE | | CODE EXCEPTION WILL BE REQUIRED AT THE | | BUREAU OF FIRE PREVENTION. | | | | 2) PLEASE SEE BUILDING REVIEW COMMENT | | #11 IN REFERENCE TO THE APPROVED FIRE | | TESTING. PLEASE SUBMIT INFORMATION | | REGARDING HOW THIS TEST WILL BE | | APPLICABLE TO THIS PROJECT AS DIFFERENT | | MATERIALS PRODUCE DIFFERENT TEST | | RESULTS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|