Plan Review Notes
Plan Review Notes For Permit 06050695
Permit Number 06050695
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-21 00:00:00***DENIED***
  
 1) CONTRACT PROPOSAL INDICATES A TOTAL
 OF (24) FIRE SPRINKLER RELOCATIONS
 WITHIN THE SCOPE OF THIS PROJECT.
 SEPARATE SHOP DRAWINGS AND PERMIT IS
 REQUIRED. A (2) HOUR PRESSURE TEST SHALL
 BE DONE UNLESS THE SPRINKLER SYSTEM
 CAN'T BE ISOLATED. IF THAT CONDITION
 EXISTS, A LETTER STATING THIS WITH THE
 CODE EXCEPTION WILL BE REQUIRED AT THE
 BUREAU OF FIRE PREVENTION.
  
 2) PLEASE SEE BUILDING REVIEW COMMENT
 #11 IN REFERENCE TO THE APPROVED FIRE
 TESTING. PLEASE SUBMIT INFORMATION
 REGARDING HOW THIS TEST WILL BE
 APPLICABLE TO THIS PROJECT AS DIFFERENT
 MATERIALS PRODUCE DIFFERENT TEST
 RESULTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722