2006-05-22 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| |
| 1.)THE CBAA CASE STATES THAT FIRE |
| RESISTANCE IS REQUIRED, "APPLICANT IS TO |
| PROVIDE ENGINEERING DOCUMENTATION TO THE |
| BUILDING OFFICIAL."PROVIDE ENGINEERING |
| AS AGREED CBAA CASE 1295. |
| |
| 2.)FLORIDA STATE OR LOCAL PRODUCT |
| APPROVAL REQUIRED, FAC9B72.THE STATE |
| PRODUCT APPROVAL IS EXPIRED (2001 CODE |
| RATHER THAN FBC2004). |
| |
| |
| 3.)THE NOA STATES THAT THE PRODUCT |
| SPECIFIED IS FOR USE OVER STEEL FRAMING. |
| THE CBAA PAPERWORK INDICATES THAT THIS |
| IS OVER WOOD FRAMING.ENGINEERING, WITH |
| LOCAL PRODUCT APPROVAL APPLICATION, IS |
| REQUIRED. |
| |
| 4.) ON THE PERMIT APPLICATIN, INCLUDE |
| ALL INFORMAITON REQUIRED BY THE ATTACHED |
| POLICY.ROOF DECK TYPE IS NOT ON THE |
| APPLICATION. |
| |
| 5.)THE CBAA CASE AND PAPERWORK |
| INCLUDED REFER TO WORK WHICH IS NOT |
| WITHIN THE SCOPE OF A CCC LICENSE: FIRE |
| SPRINKLERS, FIREPROOFING OF STRUCTURAL |
| ELEMENTS, REPAIR OF WOOD FRAMING.THE |
| PLANS WHICH YOU WILL SUBMIT SHOULD MAKE |
| CLEAR THE SCOPE OF WORK UNDER THIS |
| PERMIT APPLICATION.PROVIDE APPLICATION |
| NUMBERS OF THE OTHER WORK ASSOCIATED |
| WITH THIS PROJECT, OR APPLY UNDER A |
| CONTRACTOR LICENSED TO OVERSEE ALL WORK |
| REQUIRED. |
| |
| |
| 6.)AS NO PLANS WERE SUBMITTED, CODE |
| COMPLIANCE CANNOT BE DETERMINED.BASED |
| ON THE FORMULA ON THE PRODUCT APPROVAL, |
| THIS PRODUCT DOES NOT MEET THE DESIGN |
| PRESSURE LIMITATION FOR ZONES 2 AND 3 |
| FOR A ROOF 0- 10 DEGREES. |
| |
| 7.)DESIGNER OF RECORD IS TO REVIEW THE |
| PRODUCT APPROVALS, FBC*106.3.3. |
| |
| 8.)IS THERE A WOOD DECK IN ADDITION TO |
| THE WOOD FRAMING?EXISTING CONDITIONS |
| ARE NOT CLEAR. |
| |