Plan Review Notes For Permit 06050627 |
Permit Number |
06050627 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-21 00:00:00 | ***DENIED*** | | | | 1) CALCULATION SHEETS INDICATE A SAFETY | | MARGIN OF 4.928 PSI. PLEASE NOTE THAT A | | MINIMUM SAFETY MARGIN OF 5 IS REQUIRED | | IN ACCORDANCE WITH LOCAL REQUIREMENTS. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|