Plan Review Notes
Plan Review Notes For Permit 06050627
Permit Number 06050627
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-21 00:00:00***DENIED***
  
 1) CALCULATION SHEETS INDICATE A SAFETY
 MARGIN OF 4.928 PSI. PLEASE NOTE THAT A
 MINIMUM SAFETY MARGIN OF 5 IS REQUIRED
 IN ACCORDANCE WITH LOCAL REQUIREMENTS.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved