2006-12-17 15:19:38*** UNSAT 3RD REVIEW ***
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS HAVE NOT
 YET BEEN FULLY ADDRESSED.
 PLEASE SEE NEW COMMENTS WHICH SHOULD BE NOTED AS THIS
 REVIEWER GOING THROUGH PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE AREA FOR INGRESS/EGRESS AT THE REAR
 OF BUILD OUT WHICH DOES NOT SEEM TO INDICATE ANY DEVICE
 TO TURN ON OR OFF LIGHTING AUTOMATICALLY. ( AREA
 REDLINED)
 PLEASE SEE RESPONSE AND CONVERSATION ON PHONE WITH MR.
 JIMMY EDWARDS WAS THAT METHOD "B" WAS GOING TO BE USED
 AND SUBMITTED.
 PLEASE THE ORIGINAL ENERGY CALCULATIONS DATED 5-1-06
 ARE STILL BEING ATTACHED INDICATING A METHOD "A".
 PLEASE SEE THIS DOES NOT COMPLY OR PROVIDE THE
 INFORMATION AS NEEDED AND NOTED IN PREVIOUS REVIEWS.
 PLEASE SEE THIS METHOD AS ATTACHED STILL INDICATES ALL
 LIGHTING BEING MANUALLY CONTROLLED WHICH BY PLANS AND
 DESIGN IS NOT THE CASE.
 PLEASE SEE 13-415.1.ABC.1.1, AND 13-415.2.ABC.1 FOR
 MINIMUM CALCULATIONS FOR LIGHTING POWER DENSITIES.
  
 ** NEW NOTES NOTED BY THIS REVIEWER WHICH DO NOT APPLY
 TO CHANE ENGINEERING**
  
 1) NOTE: PLEASE SEE MISSING TITLE BLOCKS FROM LANDSCAPE
 SHEETS WHICH ARE SIGNED, AND SEALED BY A LANDSCAPE
 ARCHITECT. PLEASE SEE FLORIDA ADMINISTRATIVE CODE
 61G1-16.004 AND FS 481.219
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE CIVIL ENGINEERING/SITE SHEETS.
 PLEASE SEE MISSING PRINTED NAME AND LICENSE NUMBER.
  
 ** THESE TWO COMMENTS ARE REQUIRED TO BE DONE WHETHER
 OR NOT COMMENT IS MADE BY ANY OTHER TRADE.
 PLEASE KNOW SAID INFORMATION MAY BE STAMPED, LABELED,
 OR HANDWRITTEN ON SHEETS AS LONG AS THERE ARE NOT
 COMMENTS WHICH WILL REQUIRE SHEETS TO BE CHANGED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
  
  