2006-10-28 14:02:03 | PAUL SCHMITZ |
| [email protected] |
| FBC 2004 PLUMBING CODE PLAN REVIEW |
| FBC2004 FUEL GAS CODEPLAN REVIEW |
| FBC 2004 CH 11, FL ACESSIBILITY CODE |
| AMENDMENTS TO THE FLORIDA BUILDING CODE |
| CHAPT.1, ADMINISTRATION, 2004 EDITION |
| |
| UNSAT |
| NEW COMMENT, SAYING WILL COMPLY, IS NOT ACCEPTABLE, |
| PROVIDE THE INFORMATIOIN ON THE PLANS. |
| |
| 106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN |
| UPON SUITABLE MATERIAL. CONSTRUCTION DOCUMENTS SHALL BE |
| OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| IT WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| DETERMINED BY THE BUILDING OFFICIAL (SEE ALSO SECTION |
| 106.3.5). |
| |
| |
| 1) INCLUDE NOTE BELOW ONSHT 2. DEMOLITION |
| SEC 704.5DEAD ENDS.IN THE INSTALLATION |
| OR REMOVAL OF ANY PART OF THE DRAINAGE |
| SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| |
| 2) PROVIDE THE INFORMATION AS REQUIRED FOR EACH |
| SEPERATE OCCUPANCY, (SPACE #1,#2) |
| SHT 3. SEC 403.1MINIMUM NUMBER OF |
| PLUMBING FIXTURES SHALL BE PROVIDED FOR |
| THEOCCUPANT LOAD BASED ON TABLE 403.1 |
| |
| 3) DOOR SWINGS IN CLEAR FLOOR SPACE FOR D/F BY UNISEX |
| REST RM. |
| SHT 3.SEC 410.1 DRINKING FOUNTAIN |
| |
| 4) COMPLIED |
| SHT 3. SEC 11-4.1.3 PRIVATE TOILET ROOM(DELETED) |
| |
| 5) SHOWDIMENSIONS FOR FIXTURES OFF WALLS |
| SHT 3 SEC 11-4.22, UNISEX TOILET |
| ROOM, EACH PUBLIC AND COMMON USE TOILET |
| ROOM SHALL COMPLY WITH SEC 11-4.1.3 |
| |
| 6) SHT 5. ROOF PLAN: COMPLIED |
| |
| 7) SHT 19 SEC 606.1 (4) FULLY OPEN VALVES, COMPLIED |
| |
| END OF COMMENTS QUESTIONS 561-805-6692 |