Date |
Text |
2006-10-15 14:16:59 | ********* UNSAT2ND REVIEW *********** |
| |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE |
| STILL IN NEED OF ADDRESSING ALONG WITH NEW NOTES DUE TO |
| INFORMATION NOW SHOWN OR CHANGES MADE. |
| |
| |
| 1) NOTE: NO, SAME NOTE . |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE FOLLOWING |
| MININUM CODES SHALL BE SPECIFIED ON THE |
| PLANS FOR DESIGN AND BUILDING. |
| NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| 2002. |
| |
| 2) NOTE:NO, COULD NOT LOCATE ANY INFORMATION ON |
| SUMMARY OR BREAK DOWN OFLOADS AND HOW THEY HAVE BEEN |
| FIGURED OR DERIVED? PLEASE ALSO SEE COMMENT FOR SIGN |
| CIRCUIT. PLEASE SEE BOTH ARE BEING SHOWN ON THE SAME |
| CIRCUIT NOW ON PANEL "L" WHICH PANEL "M" STILL SHOWS |
| THE CIRCUITING WHICH WAS DONE ON PREVIOUS PLANS( M-15) |
| ?? PLEASE SEE ALL NOTES PERTAINIGN TO THESE ADJUST AND |
| CORRELATE. |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE SHOW WINDOW |
| REQUIRED DEDICATED CIRCUITS MAY NOT BE |
| SHARED AS/OR WITH THE REQUIRED SIGN |
| CIRCUITS. PLEASE SHOW LOADS PER 220.12A |
| ON CALCS FOR "WATTS" PER LINEAR FT. |
| |
| 3) NOTE:NO, PLEASE SEE NOTE ABOVE, ALSO PLEASE SEE |
| 600.5, AS PERVIOUSLY NOTED FOR LOCATION(S) OF REQUIRED |
| CIRCUIT. PLEASE SEE THE SAME 600.5 WHICH REFERENCES |
| 220.3B6 FOR MIN VA REQUIRED FOR THIS. PLEASE SEE PANEL |
| SCHEDULE EITHER "M" OR "L" EACH SHOWS A 4A LOAD?? HOW |
| IS THIS POSSIBLE WHEN THE MIN VA IS REQUIRED TO BE |
| FIGURED AT 1200VA.PLEASE ADJUST. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THE REQUIRED |
| DEDICATED SIGN CIRCUITS SHALL BE SIZED |
| AND CIRCUITED PER 600.5 WHETHER OR NOT |
| AN ELECTRICAL TYPE SIGN WILL BE |
| INSTALLED. |
| |
| 4) NOTE: ? SEE NEW NOTES AS THIS NOTE WAS ADDED ON |
| PANEL SCHEDULE FOR "PLUGMOLD"?? |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE 220.12B, TRACK LTS |
| SHALL BE SHOWN IN CALCULATIONS . |
| |
| 5) NOTE:NO, SAME NOTE, ALONG WIHT NOTES ABOVE ABOUT |
| SIGNS, SHOW WINDOWS ETC, PLEASE PROVIDE A LOAD SUMMARY |
| ON HOW LOADS WERE DERIVED. SHOWING A CONNECTED AMERAGE |
| LOAD DOES NOTPROVIDE INFORMATION. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THAT LOAD |
| CALCULATIONS SHALL BE SHOWN. RECEPTS |
| WHEN KNOWN ARE TO BE SHOWN, LIGHTING |
| LOADS SHALL BE SHOWN AND IF CONTINUOUS |
| THESE SHALL BE IDENTIFIED WITH 125% FIG. |
| PLEASE SEE CALCUALTIONS WILL BE REQUIRED |
| EVEN IF NO DERATINGS ARE GOING TO BE |
| DONE. PLEASE SEE THE LOADS ON PANELS NOW |
| ARE NOT COMPLETE AT THIS TIME. |
| 220.3,220.10,220.11,220.13,, |
| 215.3,230.42 ETC. |
| 215.5 |
| |
| 6) NOTE:NO, PLEASE SEE THESE ARE STILL BEING SHOWN |
| WITH TWO SEPARATE LOADS, WHERE THE MECHANICAL PLANS |
| STILL INDICATE BOTH OF THESE BEING SAME?? |
| PLEASE ADJUST. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE CORRELATE LOADS AND OCP |
| FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2 |
| ARE THE SAME , YET THE AMPERAGE IS NOT |
| THE SAME AND THE OCP IS DIFFERENT? |
| PLEASE SEE MECHANICAL PLANS AND |
| CORRELATE. |
| PLEASE BE SURE TO SEE 424.3B FOR 125% |
| OCP MIN. |
| PLEASE ADJUST AWG PER 310.16 |
| |
| 7) NOTE:NO, THIS IS UNCLEAR AT THIS TIME AS THE |
| STAIRS AND MEZZ LEVELS ARE UNCLEAR IF THEY EVEN EXIST |
| ANYMORE AS SHEETS ARE STILL BEING SUBMITTED SHOWING A |
| MEZZ LEVEL, YET NO LIGHTING OR STAIRS ARE SHOWN?? |
| PLEASE ALSO SEE NEW NOTES. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SHOW THE NORMAL AND |
| EMERGENCY FT CANDLES FOR STAIRS. PLEASE |
| SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH |
| NOW REQUIRES 10FT CANDLES (108LUX) UNDER |
| NORMAL AND 10.8 FT CANDLES (10.8) UNDER |
| EM CONDITIONS. |
| PLEASE SHOW THE PHOTO-METRICS FOR THE |
| EGRESS PATHS TO THE PUBLIC RIGHT OF WAY |
| AS REQUIRED. |
| |
| 8) NOTE: ? NO, ?PANEL HAS NOT MOVED AND ROOM |
| DESIGNATION HAS BEEN REMOVED FROM PLANS ALL TOGETHER?? |
| THE ROOM SHALL BE IDENTIFIED ON PLANS FOR USE AND |
| OCCUPANCY. IF INDEED THIS IS GOING TO BE USED AS A |
| STORAGE ROOM, PLEASE RELOCATE PANELS AS THIS IS A LIFE |
| SAFETY ISSUE AND AT THE VERY LEAST A FIRE HAZARD TO THE |
| OCCUPANTS AND PROPERTY DAMAGE POTENTIAL. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE LOCATION OF PANEL |
| "L" SHALL NOT BE LOCATED IN STORAGE |
| ROOM. |
| PLEASE RELOCATE.110.26,408.7, 240.24 |
| ETC. |
| PLEASE ALSO SHOW SECTION #2 OF PANEL "L" |
| ON PLANS. |
| |
| 9) NOTE: OK, HOWEVER DUE TO PLANS NOT BEING COMPLETE |
| FOR CLEAR REVIEW, PLEASE SEE PLANS WHICH STILL INDICATE |
| A MEZZ LEVEL IN SETS DO NOT CONTAIN SOME ITEMS |
| IDENTIFIED TO BE ON FIXTURE SCHEDULE. FIXTURE FOR |
| POSSIBLE STAIR AREA IS NTO SHOWN, PLEASE SEE OTHER |
| NOTES FOR COORDINATION. |
| |
| ** PREIVOUS REVIEW NOTE ** |
| PLEASE COMPLETE FIXTURE |
| IDENTIFICATION ON PLANS. PLEASE SEE SOME |
| ARE MISSING FIX DESIGNATIONS. |
| PLEASE ALSO SEE SOME FIXTURES ON FIX |
| SCHEDULE COULD NOT BE LOCATED ON PLANS? |
| |
| 10) NOTE: OK. |
| |
| 11) NOTE: OK, CIRCUITING WAS COMPLETED HOWEVER WILL BE |
| REVISED BASED ON OTHER COMMENTS. |
| |
| 12) NOTE: OK, HOWEVER SEE ONE NEW NOTE AS "FYI". |
| |
| 13) NOTE: OK, HOWEVER PROVIDE A GROUNDING ELECTRODE |
| ATTACHMENT DETAIL FOR A NEW BUILDING? PLEASE KNOW IT |
| SEEMS THIS BUILDING IS EXISTING AND TO SHOW AN |
| ATTACHMENT TO THE FOOTER STEELMAY NOT BE DESIRED. |
| PLEASE KNOW ON AN EXISTING OLDER BLDG WHERE THE FOOTER |
| STEEL IS NOT AVAILABLE, IT IS NOT REQUIRED TO CHIP |
| OUT/EXPOSE THE EXISTING FOOTER STEEL (IF THERE IS ONE) |
| AS THIS MAY AFFECT THE STRUCTURAL INTEGRITY OF THE |
| EXSITING FOOTER AND HAVING TO SEAL THIS AREA BACKSO |
| THAT MOISTURE AND SPALDING DOES NOT OCCUR. PLEASE ONLY |
| INCLUDETHE LOCATIONS WHICH WILL BE AVAILABLE ETC PER |
| 250.50 2002 NEC. CODES ARE NOTE REQUIRED TO BE ON |
| DETAIL HOWEVER MAY. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SHOW THE LOCATION OF |
| THE ATTACHMENT OF THE GROUNDING |
| ELECTRODE CONDUCTOR. |
| 250.24B,250.6,215.5 |
| |
| 14) NOTE: OK, HOWEVER SEE 240.12 FOR SELECTIVE |
| COORDINATION FOR DESIGNER TO VERIFY. THISNOTE WAS FOR |
| AIC RATINGS.110.9 AND IS OK. |
| |
| |
| 15) NOTE: OK. |
| |
| 16) NOTE:NO/OK, OCCUPANT DEVICES HAVE BEEN USED AND |
| ADDED TO ALMOST ALL LOCATIONS, HOWEVER AS THE MEZZ |
| LEVEL IS NOT CLEAR THIS CAN NOT BE REVIEWED. PLEASE |
| ALSO SEE NO LIGHTING POWER DENSITIES WERE LOCATED FOR |
| MAX WATTAGE ALLOWED . 13-415.2.ABC.1 PLEASE ALSO |
| SPECIFY THE MAX TIMES ON DEVICES CHOSEN. (TIMER TYPE |
| 4HRS MAX, OS TYPE 30 MINS MAX). |
| PLEASE SEE CIRCUITING OF EM/ EXT LTS WILL BE AFFECT AS |
| SHOWN. MUST BE WIRED INTO BRANCH CIRCUIT AHEAD OF ANY |
| CONTROL DEVICE. PLEASE INDICATE. |
| |
| ** PREVIOUS REVIEW NOTE ** |
| PLEASE SEE THIS NOTE IS VERY |
| IMPORTANT AND WILL REQUIRE MANY CHANGES |
| IN THE ELECTRICAL LIGHTING SYSTEM AS |
| SHOWN. |
| PLEASE SEE FBC 2004 CHAPTER 13. PLEASE |
| SEE THIS IS NEW IN THE 2004 CODE AND |
| MANY CHANGES WERE MADE TO THE ELECTRICAL |
| SECTION FROM THE 2001 FBC. THESE CHANGES |
| BECAME FEDERALLY MANDATED IN JULY 04 FOR |
| EACH STATE TO ADOPT THESE MIN |
| REQUIREMENTS BY THE NEXT CODE CYCLE. |
| |
| **PLEASE SEE 13-101.1.3 THE ENERGY CODE |
| COMPLIANCE FORM SHALL BE "C". |
| PLEASE SEE 13-413.1.ABC.1, A WORST CASE |
| VOLTAGE DROP CALCULATION WILL BE |
| REQUIRED TO BE SHOWN ON PLANS FOR |
| FEEDERS AND BRANCH CIRCUITS. |
| PLEASE SEE 13-415.1.ABC.1.1, |
| 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL |
| OF WHICH REQUUIRES MANY ITEMS ON PLANS |
| TO BE CHANGED. PLEASE INDICATE THE TYPE |
| OF SYSTEM WHICH WILL BE USED, |
| SCHEDULING, THE LOCATIONS OF THE |
| REQUIRED OVER RIDE SWITCHES, THE |
| LOCATIONS OF THE OCCUPANCY SENSORS(IF |
| USED) AND PLEASE SEE THE REQUIREMENTS OF |
| THE MULTIPLE FLOORS. ETC |
| PLEASE BE SURE TO INCLUDE DEVICES FOR |
| SEPARATE SPACES. |
| |
| |
| 17) NOTE: OK. |
| |
| |
| 18) NOTE:NO, THIS WAS NOT DONE,. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| **PREVIOUS REVIEW NOTE ** |
| PLEASE KNOW, BEFORE |
| RESUBMITTING PLANS, PLEASE BE SURE TO |
| COMPLETELY REMOVE ANY OLD/VOIDED SHEETS |
| FROM SETS AND ONLY INSERT THE "NEW" |
| SHEETS INTO SETS FOR REVIEW AND |
| STAMPING. THIS WILL HELP TO ALLEAVAITE |
| DELAYS IN REVIEW OF SAID PROJECT. ONE |
| COPY OF THE OLD/VOIDED REMOVED SHEETS |
| SHOULD ACCOMPANY THE NEW SETS FOR |
| REFERENCE. |
| |
| ** NEW NOTES ** |
| |
| 19) NOTE: PLEASE SEE ALL NOTES ABOVE WITH REPSETC TO |
| MEZZ LEVEL AND COMPLETE PLANS ACCORDINGLY. |
| |
| 20) NOTE: ** THIS IS ONLY A NOTE: PLEASE SEE A 1/0 |
| EQUIPMENT GROUNDING CONDUCTOR IS BEING SHOWN FROM MAIN |
| TO PANEL "L". PLEASE SEE 250.122 FOR MIN REQUIRED. SIZE |
| IS MUCH LARGER THAN NEEDED, HOWEVER MAY BE USED. PLEASE |
| KNOW, IF SHOWN ON PLANS LIKE THIS, THEN THE 1/0 WILL BE |
| REQUIRED OT BE INSTALLED. THIS IS FOR INFORMATIONAL |
| PURPOSE ONLY AND DOES NOT NEED TO BE REVISED. |
| |
| 21) NOTE: PLEASE SEE A NOTE WAS ADDED TO PANEL WITH A |
| DOUBLE "* *" NEXT TO CIRCUIT FOR PLUGMOLD WHICH NOTES |
| LOADS ALL FIGURED PER 220.12B AND 150WATTS PER 2'?? |
| PLEASE SEE 220.12B IS FOR TRACK LIGHTING AND MAY NOT BE |
| USED FOR PLUGMOLD. PLEASE SEE PREVIOUS NOTE FOR LOAD |
| CALCULATIONS AND REVISE. |
| |
| 22) NOTE: PLEASE SEE FOYER/ENTRANCE AREA SHALL CONTAIN |
| AN EM LT AS THERE DOORS FROM OTHER AREAS WHICH DO |
| SUPPLY THE NEEDED ILLUMINATION FOR REQUIRED EGRESS. |
| PLEASE SEE NFPA-101 7.8, 7.9 |
| |
| 23) NOTE: PLEASE SEE COPY OF FLORIDA STATUES ATTACHED |
| 553.80(2)(B) WITH RESPECTTO REPEAT COMMENTS FOR CODE |
| COMPLIANCE. |
| |
| 24) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A |
| WATER HEATER IN A STORAGE CLOSET.PLEASE RELOCATE. |
| |
| |
| PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS/ DESIGN. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |