Plan Review Notes
Plan Review Notes For Permit 06050604
Permit Number 06050604
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-15 14:16:59********* UNSAT2ND REVIEW ***********
  
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW WHICH ARE
 STILL IN NEED OF ADDRESSING ALONG WITH NEW NOTES DUE TO
 INFORMATION NOW SHOWN OR CHANGES MADE.
  
  
 1) NOTE: NO, SAME NOTE .
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE FOLLOWING
 MININUM CODES SHALL BE SPECIFIED ON THE
 PLANS FOR DESIGN AND BUILDING.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002.
  
 2) NOTE:NO, COULD NOT LOCATE ANY INFORMATION ON
 SUMMARY OR BREAK DOWN OFLOADS AND HOW THEY HAVE BEEN
 FIGURED OR DERIVED? PLEASE ALSO SEE COMMENT FOR SIGN
 CIRCUIT. PLEASE SEE BOTH ARE BEING SHOWN ON THE SAME
 CIRCUIT NOW ON PANEL "L" WHICH PANEL "M" STILL SHOWS
 THE CIRCUITING WHICH WAS DONE ON PREVIOUS PLANS( M-15)
 ?? PLEASE SEE ALL NOTES PERTAINIGN TO THESE ADJUST AND
 CORRELATE.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE THE SHOW WINDOW
 REQUIRED DEDICATED CIRCUITS MAY NOT BE
 SHARED AS/OR WITH THE REQUIRED SIGN
 CIRCUITS. PLEASE SHOW LOADS PER 220.12A
 ON CALCS FOR "WATTS" PER LINEAR FT.
  
 3) NOTE:NO, PLEASE SEE NOTE ABOVE, ALSO PLEASE SEE
 600.5, AS PERVIOUSLY NOTED FOR LOCATION(S) OF REQUIRED
 CIRCUIT. PLEASE SEE THE SAME 600.5 WHICH REFERENCES
 220.3B6 FOR MIN VA REQUIRED FOR THIS. PLEASE SEE PANEL
 SCHEDULE EITHER "M" OR "L" EACH SHOWS A 4A LOAD?? HOW
 IS THIS POSSIBLE WHEN THE MIN VA IS REQUIRED TO BE
 FIGURED AT 1200VA.PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THE REQUIRED
 DEDICATED SIGN CIRCUITS SHALL BE SIZED
 AND CIRCUITED PER 600.5 WHETHER OR NOT
 AN ELECTRICAL TYPE SIGN WILL BE
 INSTALLED.
  
 4) NOTE: ? SEE NEW NOTES AS THIS NOTE WAS ADDED ON
 PANEL SCHEDULE FOR "PLUGMOLD"??
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 220.12B, TRACK LTS
 SHALL BE SHOWN IN CALCULATIONS .
  
 5) NOTE:NO, SAME NOTE, ALONG WIHT NOTES ABOVE ABOUT
 SIGNS, SHOW WINDOWS ETC, PLEASE PROVIDE A LOAD SUMMARY
 ON HOW LOADS WERE DERIVED. SHOWING A CONNECTED AMERAGE
 LOAD DOES NOTPROVIDE INFORMATION.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THAT LOAD
 CALCULATIONS SHALL BE SHOWN. RECEPTS
 WHEN KNOWN ARE TO BE SHOWN, LIGHTING
 LOADS SHALL BE SHOWN AND IF CONTINUOUS
 THESE SHALL BE IDENTIFIED WITH 125% FIG.
 PLEASE SEE CALCUALTIONS WILL BE REQUIRED
 EVEN IF NO DERATINGS ARE GOING TO BE
 DONE. PLEASE SEE THE LOADS ON PANELS NOW
 ARE NOT COMPLETE AT THIS TIME.
 220.3,220.10,220.11,220.13,,
 215.3,230.42 ETC.
 215.5
  
 6) NOTE:NO, PLEASE SEE THESE ARE STILL BEING SHOWN
 WITH TWO SEPARATE LOADS, WHERE THE MECHANICAL PLANS
 STILL INDICATE BOTH OF THESE BEING SAME??
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE LOADS AND OCP
 FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2
 ARE THE SAME , YET THE AMPERAGE IS NOT
 THE SAME AND THE OCP IS DIFFERENT?
 PLEASE SEE MECHANICAL PLANS AND
 CORRELATE.
 PLEASE BE SURE TO SEE 424.3B FOR 125%
 OCP MIN.
 PLEASE ADJUST AWG PER 310.16
  
 7) NOTE:NO, THIS IS UNCLEAR AT THIS TIME AS THE
 STAIRS AND MEZZ LEVELS ARE UNCLEAR IF THEY EVEN EXIST
 ANYMORE AS SHEETS ARE STILL BEING SUBMITTED SHOWING A
 MEZZ LEVEL, YET NO LIGHTING OR STAIRS ARE SHOWN??
 PLEASE ALSO SEE NEW NOTES.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE NORMAL AND
 EMERGENCY FT CANDLES FOR STAIRS. PLEASE
 SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH
 NOW REQUIRES 10FT CANDLES (108LUX) UNDER
 NORMAL AND 10.8 FT CANDLES (10.8) UNDER
 EM CONDITIONS.
 PLEASE SHOW THE PHOTO-METRICS FOR THE
 EGRESS PATHS TO THE PUBLIC RIGHT OF WAY
 AS REQUIRED.
  
 8) NOTE: ? NO, ?PANEL HAS NOT MOVED AND ROOM
 DESIGNATION HAS BEEN REMOVED FROM PLANS ALL TOGETHER??
 THE ROOM SHALL BE IDENTIFIED ON PLANS FOR USE AND
 OCCUPANCY. IF INDEED THIS IS GOING TO BE USED AS A
 STORAGE ROOM, PLEASE RELOCATE PANELS AS THIS IS A LIFE
 SAFETY ISSUE AND AT THE VERY LEAST A FIRE HAZARD TO THE
 OCCUPANTS AND PROPERTY DAMAGE POTENTIAL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LOCATION OF PANEL
 "L" SHALL NOT BE LOCATED IN STORAGE
 ROOM.
 PLEASE RELOCATE.110.26,408.7, 240.24
 ETC.
 PLEASE ALSO SHOW SECTION #2 OF PANEL "L"
 ON PLANS.
  
 9) NOTE: OK, HOWEVER DUE TO PLANS NOT BEING COMPLETE
 FOR CLEAR REVIEW, PLEASE SEE PLANS WHICH STILL INDICATE
 A MEZZ LEVEL IN SETS DO NOT CONTAIN SOME ITEMS
 IDENTIFIED TO BE ON FIXTURE SCHEDULE. FIXTURE FOR
 POSSIBLE STAIR AREA IS NTO SHOWN, PLEASE SEE OTHER
 NOTES FOR COORDINATION.
  
 ** PREIVOUS REVIEW NOTE **
 PLEASE COMPLETE FIXTURE
 IDENTIFICATION ON PLANS. PLEASE SEE SOME
 ARE MISSING FIX DESIGNATIONS.
 PLEASE ALSO SEE SOME FIXTURES ON FIX
 SCHEDULE COULD NOT BE LOCATED ON PLANS?
  
 10) NOTE: OK.
  
 11) NOTE: OK, CIRCUITING WAS COMPLETED HOWEVER WILL BE
 REVISED BASED ON OTHER COMMENTS.
  
 12) NOTE: OK, HOWEVER SEE ONE NEW NOTE AS "FYI".
  
 13) NOTE: OK, HOWEVER PROVIDE A GROUNDING ELECTRODE
 ATTACHMENT DETAIL FOR A NEW BUILDING? PLEASE KNOW IT
 SEEMS THIS BUILDING IS EXISTING AND TO SHOW AN
 ATTACHMENT TO THE FOOTER STEELMAY NOT BE DESIRED.
 PLEASE KNOW ON AN EXISTING OLDER BLDG WHERE THE FOOTER
 STEEL IS NOT AVAILABLE, IT IS NOT REQUIRED TO CHIP
 OUT/EXPOSE THE EXISTING FOOTER STEEL (IF THERE IS ONE)
 AS THIS MAY AFFECT THE STRUCTURAL INTEGRITY OF THE
 EXSITING FOOTER AND HAVING TO SEAL THIS AREA BACKSO
 THAT MOISTURE AND SPALDING DOES NOT OCCUR. PLEASE ONLY
 INCLUDETHE LOCATIONS WHICH WILL BE AVAILABLE ETC PER
 250.50 2002 NEC. CODES ARE NOTE REQUIRED TO BE ON
 DETAIL HOWEVER MAY.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SHOW THE LOCATION OF
 THE ATTACHMENT OF THE GROUNDING
 ELECTRODE CONDUCTOR.
 250.24B,250.6,215.5
  
 14) NOTE: OK, HOWEVER SEE 240.12 FOR SELECTIVE
 COORDINATION FOR DESIGNER TO VERIFY. THISNOTE WAS FOR
 AIC RATINGS.110.9 AND IS OK.
  
  
 15) NOTE: OK.
  
 16) NOTE:NO/OK, OCCUPANT DEVICES HAVE BEEN USED AND
 ADDED TO ALMOST ALL LOCATIONS, HOWEVER AS THE MEZZ
 LEVEL IS NOT CLEAR THIS CAN NOT BE REVIEWED. PLEASE
 ALSO SEE NO LIGHTING POWER DENSITIES WERE LOCATED FOR
 MAX WATTAGE ALLOWED . 13-415.2.ABC.1 PLEASE ALSO
 SPECIFY THE MAX TIMES ON DEVICES CHOSEN. (TIMER TYPE
 4HRS MAX, OS TYPE 30 MINS MAX).
 PLEASE SEE CIRCUITING OF EM/ EXT LTS WILL BE AFFECT AS
 SHOWN. MUST BE WIRED INTO BRANCH CIRCUIT AHEAD OF ANY
 CONTROL DEVICE. PLEASE INDICATE.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS NOTE IS VERY
 IMPORTANT AND WILL REQUIRE MANY CHANGES
 IN THE ELECTRICAL LIGHTING SYSTEM AS
 SHOWN.
 PLEASE SEE FBC 2004 CHAPTER 13. PLEASE
 SEE THIS IS NEW IN THE 2004 CODE AND
 MANY CHANGES WERE MADE TO THE ELECTRICAL
 SECTION FROM THE 2001 FBC. THESE CHANGES
 BECAME FEDERALLY MANDATED IN JULY 04 FOR
 EACH STATE TO ADOPT THESE MIN
 REQUIREMENTS BY THE NEXT CODE CYCLE.
  
 **PLEASE SEE 13-101.1.3 THE ENERGY CODE
 COMPLIANCE FORM SHALL BE "C".
 PLEASE SEE 13-413.1.ABC.1, A WORST CASE
 VOLTAGE DROP CALCULATION WILL BE
 REQUIRED TO BE SHOWN ON PLANS FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL
 OF WHICH REQUUIRES MANY ITEMS ON PLANS
 TO BE CHANGED. PLEASE INDICATE THE TYPE
 OF SYSTEM WHICH WILL BE USED,
 SCHEDULING, THE LOCATIONS OF THE
 REQUIRED OVER RIDE SWITCHES, THE
 LOCATIONS OF THE OCCUPANCY SENSORS(IF
 USED) AND PLEASE SEE THE REQUIREMENTS OF
 THE MULTIPLE FLOORS. ETC
 PLEASE BE SURE TO INCLUDE DEVICES FOR
 SEPARATE SPACES.
  
  
 17) NOTE: OK.
  
  
 18) NOTE:NO, THIS WAS NOT DONE,.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE KNOW, BEFORE
 RESUBMITTING PLANS, PLEASE BE SURE TO
 COMPLETELY REMOVE ANY OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE "NEW"
 SHEETS INTO SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO ALLEAVAITE
 DELAYS IN REVIEW OF SAID PROJECT. ONE
 COPY OF THE OLD/VOIDED REMOVED SHEETS
 SHOULD ACCOMPANY THE NEW SETS FOR
 REFERENCE.
  
 ** NEW NOTES **
  
 19) NOTE: PLEASE SEE ALL NOTES ABOVE WITH REPSETC TO
 MEZZ LEVEL AND COMPLETE PLANS ACCORDINGLY.
  
 20) NOTE: ** THIS IS ONLY A NOTE: PLEASE SEE A 1/0
 EQUIPMENT GROUNDING CONDUCTOR IS BEING SHOWN FROM MAIN
 TO PANEL "L". PLEASE SEE 250.122 FOR MIN REQUIRED. SIZE
 IS MUCH LARGER THAN NEEDED, HOWEVER MAY BE USED. PLEASE
 KNOW, IF SHOWN ON PLANS LIKE THIS, THEN THE 1/0 WILL BE
 REQUIRED OT BE INSTALLED. THIS IS FOR INFORMATIONAL
 PURPOSE ONLY AND DOES NOT NEED TO BE REVISED.
  
 21) NOTE: PLEASE SEE A NOTE WAS ADDED TO PANEL WITH A
 DOUBLE "* *" NEXT TO CIRCUIT FOR PLUGMOLD WHICH NOTES
 LOADS ALL FIGURED PER 220.12B AND 150WATTS PER 2'??
 PLEASE SEE 220.12B IS FOR TRACK LIGHTING AND MAY NOT BE
 USED FOR PLUGMOLD. PLEASE SEE PREVIOUS NOTE FOR LOAD
 CALCULATIONS AND REVISE.
  
 22) NOTE: PLEASE SEE FOYER/ENTRANCE AREA SHALL CONTAIN
 AN EM LT AS THERE DOORS FROM OTHER AREAS WHICH DO
 SUPPLY THE NEEDED ILLUMINATION FOR REQUIRED EGRESS.
 PLEASE SEE NFPA-101 7.8, 7.9
  
 23) NOTE: PLEASE SEE COPY OF FLORIDA STATUES ATTACHED
 553.80(2)(B) WITH RESPECTTO REPEAT COMMENTS FOR CODE
 COMPLIANCE.
  
 24) NOTE: PLEASE SEE 422.17 FOR WHAT APPEARS TO BE A
 WATER HEATER IN A STORAGE CLOSET.PLEASE RELOCATE.
  
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS/ DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  