2006-10-25 16:57:29 | PERMIT: 06050604 |
| ADD: 1810 S DIXIE HWY |
| CONT: BATTEN CONSTRUCTION |
| TEL: (561)820-0027 |
| |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2NDREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED |
| WITH THE CLERK OF THE COURT BEFORE A |
| PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| NOT ACTUALLY COMMENCED |
| WITHIN 90 DAYS AFTER THE RECORDING |
| THEREOF, SUCH NOTICE IS NULL & VOID. |
| |
| 3) SHEET# 1 CODE DATA INDICATES A |
| TYPE III BUILDING BUT NO DESIGNATION TO |
| "A" OR "B". |
| |
| 4) COMPLIED. |
| |
| 5)2ND REQUEST, SHEET 1B INDICATES AS DEPICTED A 2" DROP |
| FROM THE INTERIOR FINISH SLAB TO THE EXTERIOR OF THE |
| BUILDING. |
| SHEET# 1B INDICATES ELEVATIONS ON |
| THE INTERIOR FINISH FLOOR OF 16.76'AND |
| THE EXTERIOR ELEVATION OF 16.64'. |
| 11-4.3.8 CHANGES IN LEVEL. |
| CHANGES IN LEVELS ALONG AN ACCESSIBLE |
| ROUTE SHALL COMPLY WITH SECTION 11-4.5.2 |
| . IF AN ACCESSIBLE ROUTE HAS CHANGES IN |
| LEVEL GREATER THAN ? INCH (13 MM), THEN |
| A CURB RAMP, RAMP, ELEVATOR, OR PLATFORM |
| LIFT (AS PERMITTED IN SECTION 11-4.1.3 |
| AND 11-4.1.6 ) SHALL BE PROVIDED THAT |
| COMPLIES WITH SECTION 11-4.7 , 11-4.8 , |
| 11-4.10 , OR 11-4.11 , RESPECTIVELY. AN |
| ACCESSIBLE ROUTE DOES NOT INCLUDE |
| STAIRS, STEPS, OR ESCALATORS. SEE |
| DEFINITION OF ?EGRESS, MEANS OF? IN |
| SECTION 11-3.5 [SEE FIGURE 11-7 (C) AND |
| FIGURE 11-7 (D)]. |
| |
| 6) COMPLIED. |
| |
| 7) COMPLIED. |
| |
| 8) COMPLIED. |
| |
| 9) COMPLIED. |
| |
| 10) SHEET 3, 4 AND SHEET 11 ALL DETECT A MEZANINE |
| LEVEL. AS ASKED IN REVIEW COMMENT |
| NUMBER 1 PLEASE REMOVE ALL OLD SHEETS FROM THE PERMIT |
| PACKAGE. SHEET 11 ALSO NEEDS TO BE REMOVED. |
| |
| 11)COMPLIED, ONCE ALL REFRENCE TO MEZZANINE IS |
| REMOVED FROM PLANS. |
| |
| 12) COMPLIED, ONCE ALL REFRENCE TO MEZZANINE |
| |
| 13) 2ND REQUEST, SHEET#3 DOESN'T PROVIDE ANY CUT |
| SECTION THROUGH THE TENANT |
| SEPERATION WALL PROVIDING A 1 HR TENANT SEPERATION. |
| EITHER PROVIDE THE UL LISTING AND |
| DESCRIPTION OF WALL OR TAKE THE PERSCRIPTIVE MEETHOD IN |
| TABLE 720.1(2). |
| |
| 14) COMPLIED. |
| |
| 15) COMPLIED. |
| |
| 16) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE LEVEL |
| ARE REMOVED. |
| |
| 17)) 1209.3 MECHANICAL APPLIANCES. |
| ACCESS TO MECHANICAL APPLIANCES INSTALLED IN |
| UNDER-FLOOR AREAS, IN ATTICS SPACES AND ON ROOFS OR |
| ELEVATED STRUCTURES SHALL BE IN ACCORDANCE WITH THE |
| FLORIDA BUILDING MECHANICAL CODE. |
| |
| 18) COMPLIED ONCE ALL REFRENCES TO THE MEZZANINE ARE |
| REMOVED. |
| |
| 19) COMPLIED. |
| |
| 20) COMPLIED. |
| |
| 21) COMPLIED. |
| |
| 22) COMPLIED, ONCE ALL REFRENCES TO THE MEZZANINE ARE |
| REMOVED. |
| |
| 23)COMPLIED. |
| |
| 24) COMPLIED. |
| |
| 25) 2ND REQUEST,) WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 26)2ND REQUEST, UNTIL REVIEWD BY THE DESIGNED |
| PROFESSIONAL |
| AND SIGNED OFF ACCEPTED THIS COMMENT WILL REMAIN. FL |
| BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) FIXED WINDOWS |
| B) MULLIONS |
| C) GLAZED DOORS |
| D) HOLLOW METAL DOORS SINGLE & PAIR |
| E) ROOF ASSEMBLIES |
| 1) FLAT ROOF INSULATION |
| 2) MODIFIED SINGLE PLY |
| 3) SLOPED ROOFING APPLICATION |
| 4) ROOF TILE REPORT |
| |
| 27) THIS ROOF IS MISSING OR NOT IN |
| COMPLIANCE WITH THE FOLLOW ITEMS: |
| ___ CONTRACTOR FAILED TO SUBMIT PRODUCT APPROVALS. |
| |
| _X_ CONTRACTOR FAILED TO INDICATE WHICH |
| SYSTEM TO BE USED. |
| |
| _X_ THE SYSTEM PROVIDED HAS A LOW |
| PRESSURE FOR ZONE ___ . |
| |
| _X_ NO SYSTEMS WERE SUBMITTED IN REPORT. MISSING |
| SUBREPORTS LISTED PAGE9-18. |
| NO SUBREPORT WAS HIGHLIGHTED.WITH THE REPORT |
| SUBMITTED, THIS MAY BE A |
| SITUATION: |
| THE SYSTEM PROVIDED STATES |
| LIMITATION# 7, SHOULD THE FASTENER |
| RESISTANCE BE LESS THAN THAT |
| REQUIRED, AS DETERMINED BY THE |
| BUILDING OFFICIAL, A REVISED |
| FASTENER SPACING, PREPARED , SIGNED |
| |
| AND SEALED BY A FLORIDA REGISTERED |
| PROFESSIONAL ENGINEER, REGISTERED |
| ARCHITECT OR REGISTERED ROOF |
| CONSULTANT MAY BE SUBMITTED. |
| |
| _X_NO SUBSYSTEMS SUBMITTED, MAYBE A |
| SITUATION. |
| THE SYSTEM PROVIDED INDICATES |
| LIMITATION# 9, NO ENHANCED |
| FASTENING ALLOWED. |
| |
| _X_ HIP OR RIDGE TILE INDICATE WHAT TYPE |
| OF HIP BOARD TO BE USED, ALSO |
| INDICATE TYPE OF FASTENING. |
| CLAY AND CONCRETE ROOF TILES SHALL BE |
| FASTENED IN ACCORDANCE WITH SECTION 1609 |
| OR IN ACCORDANCE WITH FRSA/RTI |
| 07320/08/05 INSTALLATION MANUAL. |
| |
| 1507.3.8 APPLICATION. |
| TILE SHALL BE APPLIED ACCORDING TO THE MANUFACTURER?S |
| INSTALLATION INSTRUCTIONS |
| OR RECOMMENDATIONS OF THE FRSA/RTI |
| 07320/08/05. |
| |
| 28) COMPLIED. |
| |
| 29) PROVISO: TO BE CHECKED BY INSPECTOR BEFORE C.O.: |
| 804.5.1 MINIMUM CRITICAL RADIANT FLUX . |
| INTERIOR FLOOR FINISH IN VERTICAL EXITS, |
| EXIT PASSAGEWAYS AND EXIT ACCESS |
| CORRIDORS SHALL NOT BE LESS THAN CLASS I |
| IN GROUPS I-2 AND I-3 AND NOT LESS THAN |
| CLASS II IN GROUPS A, B, E, H, I- 4, M, |
| R-1, R-2 AND S. IN ALL OTHER AREAS, THE |
| INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| THE DOC FF-1 ?PILL TEST? (CPSC 16 CFR, |
| PART 1630). |