Plan Review Notes
Plan Review Notes For Permit 06050604
Permit Number 06050604
Review Stop P
Sequence Number 1
Notes
Date Text
2006-07-01 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 UNSAT
  
 1) SHT 2. DEMOLITION
 SEC 704.5DEAD ENDS.IN THE INSTALLATION
 OR REMOVAL OF ANY PART OF THE DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
  
 2) SHT 3. SEC 403.1MINIMUM NUMBER OF
 PLUMBING FIXTURES SHALL BE PROVIDED FOR
 THEOCCUPANT LOAD BASED ON TABLE 403.1
  
 3) SHT 3.SEC 410.1 DRINKING FOUNTAIN
 REQUIRED. BOTTLED WATER DISPENSER SHALL
 BE PERMITTED, FOR NOT MORE THAN 50% OF
 REQUIRED DRINKING FOUNTAINS.
  
 4) SHT 3. SEC 11-4.1.3 PRIVATE TOILET
 ROOM FOR THE OCCUPANT OF A PRIVATE
 OFFICE, SHALL BE ADAPTABLE.
  
 5) SHT 3 SEC 11-4.22, UNISEX TOILET
 ROOM, EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH SEC 11-4.1.3
  
 6) SHT 5. ROOF PLAN: SEC 1106 PROVIDE
 THE CALCULATIONS FOR THE PRIMARY AND
 SECONDARY ROOF DRAINAGE.
 TABLE 1106.2,1106.3 AND 1106.7
 PROVIDE AN ISOMETRIC DRAWING ALL PIPE
 SIZES. INCLUDE POINT OF DISPOSAL.
  
 7) SHT 19 SEC 606.1 (4) FULLY OPEN
 VALVES SHALL BE INSTALLEDON THE TOP OF
 EVERY WATER DOWN FEED PIPE.
  
 END OF COMMENTS QUESTIONS 561-805-6692