2006-06-23 00:00:00*** DENIED ***
 1) AHU #1 SHOW SIZE OF MAIN RETURN AIR
 DUCT TO 42"X24" R.A. GRILL IN MEZZANINE.
  
 2) AHU #2 SHOW SIZE OF MAIN RETURN AIR
 DUCT FROM AHU TO 12"X8" DUCTS.
  
 3) AHU #3 SUPPLY AIR TO OFFICE CAN NOT
 RETURN TO AHU #1, 10'X10" TRANSFER GRILL
 DOES NOT OPEN TO AHU #3 ZONE.
  
 4) A/C SUPPLY AIR DUCT AND RETURN AIR
 TRANSFER GRILL GOING TO LOBBY ARE
 PENETRATING A FIRE RATED WALL, AND
 REQUIRE FIRE DAMPERS, PER 2004 FBC/M 607
  
 5) SEE BUILDING REVIEW NOTES #23 & #24.
  
 MECHANICAL PLAN REVIEW BY;