Plan Review Notes
Plan Review Notes For Permit 06050604
Permit Number 06050604
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-06-16 00:00:001. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 2. DEBRIS SHALL BE REMOVED FROM THE SITE
 DAILY.
  
 3. GASOLINE POWERED DEMOLITION EQUIPMENT
 SHALL NOT BE USED WITHOUT PROPER
 VENTILATION TO PREVENT CARBON MONOXIDE
 BUILD-UP OF VAPORS.
  
 4. ADDITIONAL EXIT SIGNS APPEAR TO BE
 NEEDED TO DIRECT PERSONS TO EXITS THAT
 ARE BEYOND CORNERS AND ROOMS.
  
 5. NEW STAIRS UP SHALL MEET MINIMUM CODE
 REQUIREMENTS. ANY HANDRAILS AND
 GUARDRAILS SHALL COMPLY WITH THE
 PRESCRIPTIVE STRENGTH REQUIREMENTS.
  
 6. THE MEZZANINE IS TO BE USED FOR WHAT
 PURPOSES. PLEASE INDICATE THE PURPOSE ON
 THE PLANS.
  
 7. PLEASE REVIEW DOORS SWINGS FOR
 RESTROOMS THAT OPEN ONTO THE CORRIDOR
 PROVIDING ACCESS TO THEM.
  
 8. ENSURE THAT THE EXISTING ADDRESS
 DISPLAYEED ON PAGE 6A MEETS MINIMUM CODE
 REQUIREMENTS OF AT LEAST 6" HIGH WITH
 THE PROPER WIDTH STROKE.
  
 9. FLOOR PLANS DOES NOT ILLUSTRATE ANY
 NEW OR EXISTING PORTABLE FIRE
 EXTINGUISHERS. PLEASE DISPLAY.
  
 10. PLEASE INDICATE INTERIOR FINISH FOR
 WALLS AND CEILINGS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709