2006-06-16 00:00:00 | 1. DEMOLITION, RENOVATION, AND |
| CONSTRUCTION TO COMPLY WITH NFPA 241. |
| |
| 2. DEBRIS SHALL BE REMOVED FROM THE SITE |
| DAILY. |
| |
| 3. GASOLINE POWERED DEMOLITION EQUIPMENT |
| SHALL NOT BE USED WITHOUT PROPER |
| VENTILATION TO PREVENT CARBON MONOXIDE |
| BUILD-UP OF VAPORS. |
| |
| 4. ADDITIONAL EXIT SIGNS APPEAR TO BE |
| NEEDED TO DIRECT PERSONS TO EXITS THAT |
| ARE BEYOND CORNERS AND ROOMS. |
| |
| 5. NEW STAIRS UP SHALL MEET MINIMUM CODE |
| REQUIREMENTS. ANY HANDRAILS AND |
| GUARDRAILS SHALL COMPLY WITH THE |
| PRESCRIPTIVE STRENGTH REQUIREMENTS. |
| |
| 6. THE MEZZANINE IS TO BE USED FOR WHAT |
| PURPOSES. PLEASE INDICATE THE PURPOSE ON |
| THE PLANS. |
| |
| 7. PLEASE REVIEW DOORS SWINGS FOR |
| RESTROOMS THAT OPEN ONTO THE CORRIDOR |
| PROVIDING ACCESS TO THEM. |
| |
| 8. ENSURE THAT THE EXISTING ADDRESS |
| DISPLAYEED ON PAGE 6A MEETS MINIMUM CODE |
| REQUIREMENTS OF AT LEAST 6" HIGH WITH |
| THE PROPER WIDTH STROKE. |
| |
| 9. FLOOR PLANS DOES NOT ILLUSTRATE ANY |
| NEW OR EXISTING PORTABLE FIRE |
| EXTINGUISHERS. PLEASE DISPLAY. |
| |
| 10. PLEASE INDICATE INTERIOR FINISH FOR |
| WALLS AND CEILINGS. |
| |