Notes
Date Text
2006-06-10 00:00:00IN ELEC
 ********* UNSAT ***********
  
 1) NOTE: PLEASE SEE THE FOLLOWING
 MININUM CODES SHALL BE SPECIFIED ON THE
 PLANS FOR DESIGN AND BUILDING.
 NFPA-70 2002, NFPA-101 2003, NFPA-72
 2002.
  
 2) NOTE: PLEASE SEE THE SHOW WINDOW
 REQUIRED DEDICATED CIRCUITS MAY NOT BE
 SHARED AS/OR WITH THE REQUIRED SIGN
 CIRCUITS. PLEASE SHOW LOADS PER 220.12A
 ON CALCS FOR "WATTS" PER LINEAR FT.
  
 3) NOTE: PLEASE SEE THE REQUIRED
 DEDICATED SIGN CIRCUITS SHALL BE SIZED
 AND CIRCUITED PER 600.5 WHETHER OR NOT
 AN ELECTRICAL TYPE SIGN WILL BE
 INSTALLED.
  
 4) NOTE: PLEASE SEE 220.12B, TRACK LTS
 SHALL BE SHOWN IN CALCULATIONS .
  
 5) NOTE: PLEASE SEE THAT LOAD
 CALCULATIONS SHALL BE SHOWN. RECEPTS
 WHEN KNOWN ARE TO BE SHOWN, LIGHTING
 LOADS SHALL BE SHOWN AND IF CONTINUOUS
 THESE SHALL BE IDENTIFIED WITH 125% FIG.
 PLEASE SEE CALCUALTIONS WILL BE REQUIRED
 EVEN IF NO DERATINGS ARE GOING TO BE
 DONE. PLEASE SEE THE LOADS ON PANELS NOW
 ARE NOT COMPLETE AT THIS TIME.
 220.3,220.10,220.11,220.13,,
 215.3,230.42 ETC.
 215.5
  
 6) NOTE: PLEASE CORRELATE LOADS AND OCP
 FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2
 ARE THE SAME , YET THE AMPERAGE IS NOT
 THE SAME AND THE OCP IS DIFFERENT?
 PLEASE SEE MECHANICAL PLANS AND
 CORRELATE.
 PLEASE BE SURE TO SEE 424.3B FOR 125%
 OCP MIN.
 PLEASE ADJUST AWG PER 310.16
  
 7) NOTE: PLEASE SHOW THE NORMAL AND
 EMERGENCY FT CANDLES FOR STAIRS. PLEASE
 SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH
 NOW REQUIRES 10FT CANDLES (108LUX) UNDER
 NORMAL AND 10.8 FT CANDLES (10.8) UNDER
 EM CONDITIONS.
 PLEASE SHOW THE PHOTO-METRICS FOR THE
 EGRESS PATHS TO THE PUBLIC RIGHT OF WAY
 AS REQUIRED.
  
 8) NOTE: PLEASE SEE LOCATION OF PANEL
 "L" SHALL NOT BE LOCATED IN STORAGE
 ROOM.
 PLEASE RELOCATE.110.26,408.7, 240.24
 ETC.
 PLEASE ALSO SHOW SECTION #2 OF PANEL "L"
 ON PLANS.
  
 9) NOTE: PLEASE COMPLETE FIXTURE
 IDENTIFICATION ON PLANS. PLEASE SEE SOME
 ARE MISSING FIX DESIGNATIONS.
 PLEASE ALSO SEE SOME FIXTURES ON FIX
 SCHEDULE COULD NOT BE LOCATED ON PLANS?
  
 10) NOTE: PLEASE IDENTIFY ALL FIXTURES
 WHICH ARE EM TYPE, WITH THE REQUIRED
 NOTED BATTERY BACK UP.
 215.5
  
 11) NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS. PLEASE BE SURE TO SEE 700.12E
 FOR EM/EXT LTS WHICH ARE REQUIRED TO BE
 CIRCUITED TO THE NORMAL BRANCH CIRCUIT
 IN THE AREA IN WHICH THESE FIXTURES ARE
 LOCATED.
  
 12) NOTE: PLEASE COMPLETE RISER DIAGRAM.
 PLEASE INCLUDE ALL SEC'S ON RISER FROM
 METER TO GUTTER AND FROM GUTTER TO EACH
 MAIN(S).
 310.16,215.5
  
 13) NOTE: PLEASE SHOW THE LOCATION OF
 THE ATTACHMENT OF THE GROUNDING
 ELECTRODE CONDUCTOR.
 250.24B,250.6,215.5
  
 14) NOTE: PLEASE INDICATE THE AIC
 RATINGS FOR ALL SERVICE EQUIPMENT PER
 110.9, 215.5
 THIS IS SHOWN FOR PANELS, BUT NOT FOR
 MAINS??
  
 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 FOR ALL CIRCUITS. PLEASE KNOW, THE AREA,
 ROOM, IDENTIFICATION OF EACH CIRCUIT IS
 REQUIRED. IE: CONFERENCE RM RECEPTS,
 OFFICE #2 RECEPTS, BREAK RM RECEPTS,,
 ETC ETC.
 PLEASE KNOW, GENERAL "RECEPTS" OR
 "LIGHTS" ARE NO LONGER ACCEPTABLE.408.4,
 215.5
 ** PLEASE KNOW, IT IS KNOWN AND COMMON
 THAT THESE WILL CHANGE DURING THE
 CONSTRUCTION AND WILL BE REQUIED TO BE
 REVISED ALONG WITH ANY OTHER CHANGES AT
 A LATER DATE. THIS IS HOWEVER REQ'D AT
 THIS TIME. PLEASE BE SURE ALL AREA AND
 ROOM DESIGNATIONS ARE ON PLANS.
  
 16) NOTE: PLEASE SEE THIS NOTE IS VERY
 IMPORTANT AND WILL REQUIRE MANY CHANGES
 IN THE ELECTRICAL LIGHTING SYSTEM AS
 SHOWN.
 PLEASE SEE FBC 2004 CHAPTER 13. PLEASE
 SEE THIS IS NEW IN THE 2004 CODE AND
 MANY CHANGES WERE MADE TO THE ELECTRICAL
 SECTION FROM THE 2001 FBC. THESE CHANGES
 BECAME FEDERALLY MANDATED IN JULY 04 FOR
 EACH STATE TO ADOPT THESE MIN
 REQUIREMENTS BY THE NEXT CODE CYCLE.
  
 **PLEASE SEE 13-101.1.3 THE ENERGY CODE
 COMPLIANCE FORM SHALL BE "C".
 PLEASE SEE 13-413.1.ABC.1, A WORST CASE
 VOLTAGE DROP CALCULATION WILL BE
 REQUIRED TO BE SHOWN ON PLANS FOR
 FEEDERS AND BRANCH CIRCUITS.
 PLEASE SEE 13-415.1.ABC.1.1,
 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL
 OF WHICH REQUUIRES MANY ITEMS ON PLANS
 TO BE CHANGED. PLEASE INDICATE THE TYPE
 OF SYSTEM WHICH WILL BE USED,
 SCHEDULING, THE LOCATIONS OF THE
 REQUIRED OVER RIDE SWITCHES, THE
 LOCATIONS OF THE OCCUPANCY SENSORS(IF
 USED) AND PLEASE SEE THE REQUIREMENTS OF
 THE MULTIPLE FLOORS. ETC
 PLEASE BE SURE TO INCLUDE DEVICES FOR
 SEPARATE SPACES.
  
  
 17) NOTE: PLEASE SEE THIS COMMENT IS NOT
 FOR ELECTRICAL ENGINEER.
 PLEASE SEE ALL COPIES OF PLANS DONE BY
 AN ENGINEER IS REQUIRED TO CONTAIN AND
 ORIGINAL SIGNATURE AND SEAL AND DATE.
 PLEASE SEE DRAINAGE CALCUALTIONS WHICH
 ARE "PHOTO-COPIES" OF SIGNED AND SEALED
 SHEETS. THIS IS REQUIRED PER FAC
 61G15-23.002, FS 471.025 WHETHER OR NOT
 COMMENT IS MADE BY OTHER
 ENGINEERING/CIVIL REVIEWER.
  
  
 18) NOTE: PLEASE KNOW, BEFORE
 RESUBMITTING PLANS, PLEASE BE SURE TO
 COMPLETELY REMOVE ANY OLD/VOIDED SHEETS
 FROM SETS AND ONLY INSERT THE "NEW"
 SHEETS INTO SETS FOR REVIEW AND
 STAMPING. THIS WILL HELP TO ALLEAVAITE
 DELAYS IN REVIEW OF SAID PROJECT. ONE
 COPY OF THE OLD/VOIDED REMOVED SHEETS
 SHOULD ACCOMPANY THE NEW SETS FOR
 REFERENCE.
  
  
 PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS/ DESIGN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE NAY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  