2006-06-10 00:00:00 | IN ELEC |
| ********* UNSAT *********** |
| |
| 1) NOTE: PLEASE SEE THE FOLLOWING |
| MININUM CODES SHALL BE SPECIFIED ON THE |
| PLANS FOR DESIGN AND BUILDING. |
| NFPA-70 2002, NFPA-101 2003, NFPA-72 |
| 2002. |
| |
| 2) NOTE: PLEASE SEE THE SHOW WINDOW |
| REQUIRED DEDICATED CIRCUITS MAY NOT BE |
| SHARED AS/OR WITH THE REQUIRED SIGN |
| CIRCUITS. PLEASE SHOW LOADS PER 220.12A |
| ON CALCS FOR "WATTS" PER LINEAR FT. |
| |
| 3) NOTE: PLEASE SEE THE REQUIRED |
| DEDICATED SIGN CIRCUITS SHALL BE SIZED |
| AND CIRCUITED PER 600.5 WHETHER OR NOT |
| AN ELECTRICAL TYPE SIGN WILL BE |
| INSTALLED. |
| |
| 4) NOTE: PLEASE SEE 220.12B, TRACK LTS |
| SHALL BE SHOWN IN CALCULATIONS . |
| |
| 5) NOTE: PLEASE SEE THAT LOAD |
| CALCULATIONS SHALL BE SHOWN. RECEPTS |
| WHEN KNOWN ARE TO BE SHOWN, LIGHTING |
| LOADS SHALL BE SHOWN AND IF CONTINUOUS |
| THESE SHALL BE IDENTIFIED WITH 125% FIG. |
| PLEASE SEE CALCUALTIONS WILL BE REQUIRED |
| EVEN IF NO DERATINGS ARE GOING TO BE |
| DONE. PLEASE SEE THE LOADS ON PANELS NOW |
| ARE NOT COMPLETE AT THIS TIME. |
| 220.3,220.10,220.11,220.13,, |
| 215.3,230.42 ETC. |
| 215.5 |
| |
| 6) NOTE: PLEASE CORRELATE LOADS AND OCP |
| FOR ALL AHU'S. PLEASE SEE UNIT 1 AND 2 |
| ARE THE SAME , YET THE AMPERAGE IS NOT |
| THE SAME AND THE OCP IS DIFFERENT? |
| PLEASE SEE MECHANICAL PLANS AND |
| CORRELATE. |
| PLEASE BE SURE TO SEE 424.3B FOR 125% |
| OCP MIN. |
| PLEASE ADJUST AWG PER 310.16 |
| |
| 7) NOTE: PLEASE SHOW THE NORMAL AND |
| EMERGENCY FT CANDLES FOR STAIRS. PLEASE |
| SEE NFPA-101 2003, 708.1.3,709.2.2 WHICH |
| NOW REQUIRES 10FT CANDLES (108LUX) UNDER |
| NORMAL AND 10.8 FT CANDLES (10.8) UNDER |
| EM CONDITIONS. |
| PLEASE SHOW THE PHOTO-METRICS FOR THE |
| EGRESS PATHS TO THE PUBLIC RIGHT OF WAY |
| AS REQUIRED. |
| |
| 8) NOTE: PLEASE SEE LOCATION OF PANEL |
| "L" SHALL NOT BE LOCATED IN STORAGE |
| ROOM. |
| PLEASE RELOCATE.110.26,408.7, 240.24 |
| ETC. |
| PLEASE ALSO SHOW SECTION #2 OF PANEL "L" |
| ON PLANS. |
| |
| 9) NOTE: PLEASE COMPLETE FIXTURE |
| IDENTIFICATION ON PLANS. PLEASE SEE SOME |
| ARE MISSING FIX DESIGNATIONS. |
| PLEASE ALSO SEE SOME FIXTURES ON FIX |
| SCHEDULE COULD NOT BE LOCATED ON PLANS? |
| |
| 10) NOTE: PLEASE IDENTIFY ALL FIXTURES |
| WHICH ARE EM TYPE, WITH THE REQUIRED |
| NOTED BATTERY BACK UP. |
| 215.5 |
| |
| 11) NOTE: PLEASE COMPLETE ALL CIRCUITING |
| ON PLANS. PLEASE BE SURE TO SEE 700.12E |
| FOR EM/EXT LTS WHICH ARE REQUIRED TO BE |
| CIRCUITED TO THE NORMAL BRANCH CIRCUIT |
| IN THE AREA IN WHICH THESE FIXTURES ARE |
| LOCATED. |
| |
| 12) NOTE: PLEASE COMPLETE RISER DIAGRAM. |
| PLEASE INCLUDE ALL SEC'S ON RISER FROM |
| METER TO GUTTER AND FROM GUTTER TO EACH |
| MAIN(S). |
| 310.16,215.5 |
| |
| 13) NOTE: PLEASE SHOW THE LOCATION OF |
| THE ATTACHMENT OF THE GROUNDING |
| ELECTRODE CONDUCTOR. |
| 250.24B,250.6,215.5 |
| |
| 14) NOTE: PLEASE INDICATE THE AIC |
| RATINGS FOR ALL SERVICE EQUIPMENT PER |
| 110.9, 215.5 |
| THIS IS SHOWN FOR PANELS, BUT NOT FOR |
| MAINS?? |
| |
| 15) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| FOR ALL CIRCUITS. PLEASE KNOW, THE AREA, |
| ROOM, IDENTIFICATION OF EACH CIRCUIT IS |
| REQUIRED. IE: CONFERENCE RM RECEPTS, |
| OFFICE #2 RECEPTS, BREAK RM RECEPTS,, |
| ETC ETC. |
| PLEASE KNOW, GENERAL "RECEPTS" OR |
| "LIGHTS" ARE NO LONGER ACCEPTABLE.408.4, |
| 215.5 |
| ** PLEASE KNOW, IT IS KNOWN AND COMMON |
| THAT THESE WILL CHANGE DURING THE |
| CONSTRUCTION AND WILL BE REQUIED TO BE |
| REVISED ALONG WITH ANY OTHER CHANGES AT |
| A LATER DATE. THIS IS HOWEVER REQ'D AT |
| THIS TIME. PLEASE BE SURE ALL AREA AND |
| ROOM DESIGNATIONS ARE ON PLANS. |
| |
| 16) NOTE: PLEASE SEE THIS NOTE IS VERY |
| IMPORTANT AND WILL REQUIRE MANY CHANGES |
| IN THE ELECTRICAL LIGHTING SYSTEM AS |
| SHOWN. |
| PLEASE SEE FBC 2004 CHAPTER 13. PLEASE |
| SEE THIS IS NEW IN THE 2004 CODE AND |
| MANY CHANGES WERE MADE TO THE ELECTRICAL |
| SECTION FROM THE 2001 FBC. THESE CHANGES |
| BECAME FEDERALLY MANDATED IN JULY 04 FOR |
| EACH STATE TO ADOPT THESE MIN |
| REQUIREMENTS BY THE NEXT CODE CYCLE. |
| |
| **PLEASE SEE 13-101.1.3 THE ENERGY CODE |
| COMPLIANCE FORM SHALL BE "C". |
| PLEASE SEE 13-413.1.ABC.1, A WORST CASE |
| VOLTAGE DROP CALCULATION WILL BE |
| REQUIRED TO BE SHOWN ON PLANS FOR |
| FEEDERS AND BRANCH CIRCUITS. |
| PLEASE SEE 13-415.1.ABC.1.1, |
| 13-415.1.ABC.1.2, 13-415.1.ABC.1.3, ALL |
| OF WHICH REQUUIRES MANY ITEMS ON PLANS |
| TO BE CHANGED. PLEASE INDICATE THE TYPE |
| OF SYSTEM WHICH WILL BE USED, |
| SCHEDULING, THE LOCATIONS OF THE |
| REQUIRED OVER RIDE SWITCHES, THE |
| LOCATIONS OF THE OCCUPANCY SENSORS(IF |
| USED) AND PLEASE SEE THE REQUIREMENTS OF |
| THE MULTIPLE FLOORS. ETC |
| PLEASE BE SURE TO INCLUDE DEVICES FOR |
| SEPARATE SPACES. |
| |
| |
| 17) NOTE: PLEASE SEE THIS COMMENT IS NOT |
| FOR ELECTRICAL ENGINEER. |
| PLEASE SEE ALL COPIES OF PLANS DONE BY |
| AN ENGINEER IS REQUIRED TO CONTAIN AND |
| ORIGINAL SIGNATURE AND SEAL AND DATE. |
| PLEASE SEE DRAINAGE CALCUALTIONS WHICH |
| ARE "PHOTO-COPIES" OF SIGNED AND SEALED |
| SHEETS. THIS IS REQUIRED PER FAC |
| 61G15-23.002, FS 471.025 WHETHER OR NOT |
| COMMENT IS MADE BY OTHER |
| ENGINEERING/CIVIL REVIEWER. |
| |
| |
| 18) NOTE: PLEASE KNOW, BEFORE |
| RESUBMITTING PLANS, PLEASE BE SURE TO |
| COMPLETELY REMOVE ANY OLD/VOIDED SHEETS |
| FROM SETS AND ONLY INSERT THE "NEW" |
| SHEETS INTO SETS FOR REVIEW AND |
| STAMPING. THIS WILL HELP TO ALLEAVAITE |
| DELAYS IN REVIEW OF SAID PROJECT. ONE |
| COPY OF THE OLD/VOIDED REMOVED SHEETS |
| SHOULD ACCOMPANY THE NEW SETS FOR |
| REFERENCE. |
| |
| |
| PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS/ DESIGN. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE NAY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |