Plan Review Notes
Plan Review Notes For Permit 06050590
Permit Number 06050590
Review Stop E
Sequence Number 3
Notes
Date Text
2006-11-17 15:16:21**** UNSAT 3RD REVIEW ****
  
 ***PLEASE SEE SOME NOTE FROM PREVIOUS REVIEW(S).
  
 1) NOTE:PLEASE SUBMIT PLANS SPECS/MANUFACTURE CUT
 SHEETS INTO THREE COMPLETE SETS, AS THREE SETS OF
 ELECTRICAL PLANS ARE BEING SUBMITTED, PLEASE ALSO
 SUBMIT THREE SETS OF ALL FOR STAMPING.
 PLEASE SUBMIT ALL PLANS IN A NEAT AND ORDERLY FASHION.
  
 ONLY ONE SET OF EACH OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE. THESE SHALL BE LABELED
 "VOIDED/OLD" AND SHOULD BE PLACED TOGETHER SEPARATE
 FROM NEW SETS.
 ANY COMMENT RESPONSE LETTERS FRO DESIGN PROFESSIONAL
 SHALL BE KEPT SEPARATELY.
 THIS WAS REQUESTED ON PREVIOUS REVIEW.
  
 2) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEWS, THE
 ELECTRICAL CONTRACTOR HAS NOT SIGNED ON THE ELECTRICAL
 LINE OF PERMIT APPLICATION FOR THE ELECTRICAL PERMIT AS
 PART OF THIS PACKAGE. IF THIS ELECTRICAL CONTRACTOR IS
 NOT DOING THE ELECTRICAL INSTALLATION AS SUBMITTED
 WHICH IS HIGHLY UNLIKELY, THEN PLEASE KNOW SEPARATE
 PERMIT APPLICATION WILL BE REQUIRED WITH SEPARATE FEES.
 THIS IS THE LAST NOTICE WHICH WILL BE GIVEN TO THIS.
  
 3) NOTE: PLEASE SEE FLOOR /SITE PLANS DO NOT CORRELATE
 WITH RISER DIAGRAM SUBMITTED. PLEASE SEE FIRST FLOOR
 ELECTRICAL ROOM IS NOT SHOWN ON E-2, AND THE FEEDERS DO
 NOT SHOW THESE GOING TO ANY DISCONNECTING MEANS AT THIS
 BUILDING WHICH IS PARTIALLY SHOWN ON RISER.
 225.31-225.39.
 PLEASE SEE PREVIOUS NOTES.
  
 4) NOTE: PLEASE SEE PREVIOUS NOTES FOR DETAILS WHICH IS
 REQUIRED PER NFPA-110 PLEASE SEE SECTIONS BELOW AS
 PLANS DO NOT PROVIDE ENOUGH INFORMATION FOR SEPARATION,
 ISOLATION, ETC. FROM THE STRUCTURAL ELEMENTS OF THE
 BUILDING.
 PLEASE SEE NFPA-110 2002 7.3, .4, .5, .6, .7 ETC.
 THIS WAS PAST BY THE BUILDING REVIEWER , HOWEVER IS
 STILL REQUIRED.
  
 ** ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
 **IF THERE ARE ANY QUESTIONS, COMMENTSOR IF ANY OF
 THE NOTES TYPEDWHICH ARE UNCLEAR IN ANY WAY, PLEASE
 DO NOT HESITATEIN CONTACTING THIS REVIEWER.
  
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  