2006-08-16 00:00:00 | *** UNSAT 2ND REVIEW *** |
| |
| 1) NOTE: PLEASE SEE MAINS AND |
| DISCONNECTING MEANS FOR FEEDERES AND |
| SEC'S SHALL BE GROUPED. THE MAINS ARE |
| NOT GROUPED AND HAVING A BREAKER ON THE |
| GEN IN THE GARAGE OR THE MAIN IN SB8 IS |
| NOT PERMITTED. |
| PLEASE SEE 225.31-225.39, 230.72 ETC. |
| PLEASE KNOW THAT A DISCONNECTING MEANS |
| FOR THE FEEDERS FROM THE GEN WILL BE |
| REQUIRED IN CLOSE PROXIMITY TO THE |
| EXISTING MAINS/DISCONNECTS. |
| PLEASE ALSO KNOW THAT THE ATS IS NOT |
| PERMITTED IN THE MECHANICAL EQUIPMENT |
| ROOM AND SHALL BE LOCATED IN THE |
| ELECTRICAL ROOM WITH OTHER ELECTRICAL |
| EQUIPMENT WHICH IS IS BEIGN FED FROM AND |
| WHICH IT IS FEEDING. |
| |
| |
| 2) NOTE: PLEASE SEE REVIEW COMMENTS FROM |
| OTHER TRADES AS THE LOCATION OF THE |
| GENERATOR IN THE PARKING GARAGE DOES NOT |
| PROVIDE ENOUGH INFORMATION FOR |
| SEPARATION, ISOLATION, ETC. |
| PLEASE SEE NFPA-110 2002 7.3,.4,.5,.6,.7 |
| ETC. |
| |
| 3) NOTE: PLEASE KNOW THAT ONLY TWO SETS |
| OF ELECTRICAL PLANS ARE REQUIRED, |
| HOWEVER THREE SETS ARE BEING SUBMITTED. |
| IF SUBMITTING THREE FOR STAMPING, THEN |
| PLEASE BE SURE THE THIRD SET IS SIGNED, |
| DATED AND SEALED. |
| FS 471.025, FAC 61G15-23.002 |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |