Plan Review Notes For Permit 06050590 |
Permit Number |
06050590 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-06-16 00:00:00 | 1. THE PLANS INDICATE THAT A NEW | | GENERATOR IS PLANNED FOR THE SECOND | | FLOOR GENERATOR ROOM OF THE PARKING | | GARAGE. INFORMATION INDICATES THAT THE | | GENERATOR IS TO BE SUPPLIED BY NATURAL | | GAS. NO DETAILS PROVIDED ON WHERE THE | | PROPOSED INSTALLATION ROOM IS LOCATED | | WITHIN THE GARAGE. | | | | 2. NO DETAILS PROVIDED WITH REGARDS TO | | VENTING OF THE GENERATOR WHILE IT IS | | RUNNING. THE TERMINATION POINT OF THE | | EXHAUST IS TO BE SHOWN SO A BACK FEED OF | | DANGEROUS FUMES DOES NOT OCCUR. | | SOMETIMES ARCHITECTURAL ELEMENTS OF A | | BUILDING CAN CAUSE THIS TO OCCUR. | | | | 3. WILL CONTROL PANELS BE PROVIDED IN | | THE FIRE COMMAND ROOM TO ADVISE STATUS | | OF THE SYSTEM. | | | | 4. WHAT OTHER EQUIPMENT WILL BE | | CONTAINED WITHIN THE ROOM WHERE THE | | GENERATOR IS PLANNED. | | | | 5. MORE DETAILS ARE NEEDED FOR THE PLAN | | REVIEW PROCESS. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 804-4709 |
|