2006-06-16 00:00:001. THE PLANS INDICATE THAT A NEW
 GENERATOR IS PLANNED FOR THE SECOND
 FLOOR GENERATOR ROOM OF THE PARKING
 GARAGE. INFORMATION INDICATES THAT THE
 GENERATOR IS TO BE SUPPLIED BY NATURAL
 GAS. NO DETAILS PROVIDED ON WHERE THE
 PROPOSED INSTALLATION ROOM IS LOCATED
 WITHIN THE GARAGE.
  
 2. NO DETAILS PROVIDED WITH REGARDS TO
 VENTING OF THE GENERATOR WHILE IT IS
 RUNNING. THE TERMINATION POINT OF THE
 EXHAUST IS TO BE SHOWN SO A BACK FEED OF
 DANGEROUS FUMES DOES NOT OCCUR.
 SOMETIMES ARCHITECTURAL ELEMENTS OF A
 BUILDING CAN CAUSE THIS TO OCCUR.
  
 3. WILL CONTROL PANELS BE PROVIDED IN
 THE FIRE COMMAND ROOM TO ADVISE STATUS
 OF THE SYSTEM.
  
 4. WHAT OTHER EQUIPMENT WILL BE
 CONTAINED WITHIN THE ROOM WHERE THE
 GENERATOR IS PLANNED.
  
 5. MORE DETAILS ARE NEEDED FOR THE PLAN
 REVIEW PROCESS.
  
 MIKE CARSILLO, CHIEF FIRE PREVENTION
 OFFICER
 804-4709