Plan Review Notes
Plan Review Notes For Permit 06050590
Permit Number 06050590
Review Stop E
Sequence Number 1
Notes
Date Text
2006-06-11 00:00:00********** UNSAT *************
  
 ** PLEASE KNOW BESIDES THE BELOW
 COMMENTS, PLANS ARE NOT COMPLETE AT THIS
 TIME FOR COMPLETE REVIEW.
  
  
 1) NOTE: ATTENTION CONTRACTOR, IF PROTON
 ELECTRICAL IS ALSO DOING THE ELECTRICAL
 INSTALLATION FOR THE CONNECTIONS ON THE
 GENERATOR, THEN PLEASE SIGN ON THE
 ELECTRICAL LINE ON PERMIT APPLICATION SO
 AN ELECTRICAL PERMIT CAN BE ESTABLISHED.
 THIS WAS NOT
  
 2) NOTE: PLEASE SUBMIT SPECS FOR FUEL
 TANK. PLEASE SEE PLANS MUST INCLUDED
 LOCATION, VENTILATION, FIRE RATINGS ETC
 .
 PLEASE SEE NOTE #5 BELOW, IF THE GEN
 FEEDS ANY LEGALLY REQUIRED BACK UP
 LTS/SYSTEMS, THE AMOUNT OF FUEL, AND RUN
 TIMES SHALL BE CLEARLY INDICATED ON
 PLANS.
 PLEASE KNOW THERE IS NOTHING ON PLANS
 FOR INSTALLATIONOF GEN, FUEL, LOCATION
 ETC.
 PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT PLANS SUBMITTED.
 PLEASE BE SURE ALL TANK SPECS CONTAIN
 LISTING BY A NRTL.
 215.5
  
 3) NOTE: PLEASE SUBMIT A COMPLETEPLAN
 SHOWING THE LAYOUT FOR THE GENERATOR.
 PLEASE SEE THAT NO MEANS OF DISCOONECTS
 ARE BEING SHOWN FOR GROUPING OF MAINS IN
 THE BUILDING.
 PLEASE SHOW THE LOCATION OF ALL THE
 EXISTING GENERATORS FEEDING THIS
 BUILDING THE MEANS OF DICONNECT LOCAITON
 FOR ALL.
 230.72, 225.31-225.39, 230.2
  
 4) NOTE: PLEASE SEE THAT ALL SPECS
 SUBMITTED FOR GEN, ATS ETC SHALL CLEARLY
 BE HIGHLIGHTED FOR EACH UNIT EQUIPMENT
 BEING USED ON THIS JOBSITE.
 215.5
  
 5) NOTE: PLEASE VERIFY IF THIS GENERATOR
 WILL BE FEEDING ANY OF THE REQUIRED BACK
 UP POWER FROM LIGHTING ETC.
 PLEASE NOTE IF ALL LTS ARE BATTERY BACK
 UP, OR ARE THEY FED FROM A LEGALLY
 REQUIRED BACK UP SYSTEM NOW.
 PLEASE SEE SYSTEM INSTALLATION
 REQUIREMENTS PER 700,701, NFPA-110 ETC
  
  
 6) NOTE: PLEASE SEE PLANS INDICATE TWO
 TRANSFORMERS BEING FED, YET PANEL SB8
 DOES NOT CORRELATE.
 215.5
  
 7) NOTE: PLEASE PLACE NOTES ON PLANS FOR
 ALL SIGNAGE WHICH WILL BE REQUIRED.
 230.2E,702.8,701.9 ETC.
 PLEASE KNOW, THE LOCATIONS OF SUCH
 DISCONNECTS AND SYSTEMS HAVE NOT BEEN
 APPROVED AT THIS TIME.
  
 8) NOTE: PLEASE INDICATE THE OCP AT
 GENERATOR.
 215.5
  
 9) NOTE: PLEASE SEE MULTIPLE PANELS ON
 RISER WITH THE SAME IDENTIFICATION??
  
 10) NOTE: PLEASE SEE THAT ALL CONTINUOUS
 LOADS SHALL BE SHOWN AT 125%.
 215.3,230.42 ETC
  
 11) NOTE: PLEASE SEE MAX HEAT LOADS
 SHALL BE FIGURED FOR THE AHU'S OR LOAD
 SHEDDING IS PERMITTED. PLEASE PROVIDE A
 COMPLETE DETAIL FOR LOAD SHEDDING IF
 THIS OPTION IS TAKEN.
 THE WIRING SCHEMATIC WILL BE REQUIRED ON
 PLANS.
 702.5 ETC
  
 12) NOTE: PLEASE SEE GEN ANNUNCIATOR
 PANEL, CONTROLS,STATUS INDICATORS SHALL
 ALSO BE LOCATED IN THE EXISTING FIRE
 COMMAND ROOM WITH SIGNAGE AS REQUIRED.
 NFPA-72, NFPA-101, NFPA-110
  
 13) NOTE: PLEASE KNOW, A FUEL TYPE
 PERMIT MAY ALSO BE REQUIRED. SEE MECH
 REVIEW.
  
 14) NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTORS.
 250.110,250.122,250.6,250.24.
 PLEASE SEE NONE ARE BEING SHOWN AT THIS
 TIME. PLEASE KNOW, IF USING ALL METAL
 CONDUITS, THEN CONNECTORS ALL SHALL BE
 LISTED FOR "EQUIPMENT GROUNDING".
 STANDARD CONNECTORS ARE NO PERMITTED
 UNLESS LISTED AS NOTED.OR
 PLEASE INDICATE THE EQUIPMENT GROUNDING
 CONDUCTOR SIZED PER 250.122
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES
 WHICH WILL AFFECT THE PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.