Plan Review Notes For Permit 06050541 |
Permit Number |
06050541 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-31 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2004 | | | | 1.)CODE COMPLIANCE CANNOT BE | | DETERMINED DUE TO CONFLICTING | | INFORMATION IN THE PERMIT PACKAGE. | | | | YOU HAVE DECLARED WIND PRESSURES USING | | SOFTWARE; THESE PRESSURES APPEAR | | COMPLIANT.ON THE PRODUCT APPROVAL, YOU | | HAVE CIRCLED -31.2, WHICH IS TOO LOW FOR | | 140MPH. | | | | YOU HAVE CIRCLED THE NUMBER -31.2 IN | | SEVERAL DIFFERENT PLACES, SHOWING TWO | | DIFFERENT EDGE DISTANCES AND TWO | | DIFFERENT FASTENERS. | | | | THE SPACING OF 12"/12" SPECIFIED ON THE | | SCHEDULE IS NOT COMPLIANT FOR ALL | | OPENINGS.SEE THE ANCHOR SPACING | | REQUIRED FOR -47.2. | | |
|