Plan Review Notes For Permit 06050519 |
Permit Number |
06050519 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-08-02 00:00:00 | NONCOMPLIANT | | | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | PLEASE SUBMIT DETAILS FOR THE PANEL | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | IF THE PANEL IS EXISTING, THE ENGINEER | | NEEDS TO INDICATE SAME ON PLAN.215.5 NEC | | 2002. | | | | THE RISER SUBMITTED FOR THE SECOND | | REVIEW DOES NOT INDICATE WHERE THE POOL | | FEED FROM THE MAIN PANEL TERMINATES. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | |
|