2006-05-31 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06050482
 ADD: 1101 S FLAGLER DR BLDG "I"
 CONT: RALPH DELLA-PIETRA, INC.
 TEL: (561)745-8555
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 2) DISCREPANCY PERMIT APPLICATION
 DESCRIBES THE REMOVAL OF 5/8" CDX
 PLYWOOD AND ADDING 5/8" PLYWAOOD
 SHEATHING WHEREAS THE PLANS ONLY
 INDICATE "REMOVAL" OF PLYWOOD, NO
 MENTION OF REPLACEMENT, WHAT ABOUT SHEER
 WALLS?
  
 3) SHEET A-3 IS MISSING INFORMATION ON
 WIRE LATH:
 2510.3 INSTALLATION.
 INSTALLATION OF THESE MATERIALS SHALL BE
 IN COMPLIANCE WITH ASTM C 926 AND ASTM C
 1063.
 A) TYPE OF LATH,& WEIGHT
 B) FASTENER& SPACING
  
 4) DETAIL @ WINDOWS & DOORS.
  
 5) A-3 DISCREPANCY, SOFFITS THERE ARE
 (2) NOTES ONE FOR 3/8" EXT GRADE PLYWOOD
 FOR SOFFIT THE OTHER IS TO REMOVE AND
 STUCCO SOFFIT. PROVIDE TYPE OF LATH FOR
 SOFFITS, (24" C/C)?
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  
  