2006-08-07 00:00:00*** UNSAT 4THR REVIEW **
  
 1) NOTE: PLEASE SEE THE MTS
 SPECIFICATIONS SUBMITTED ARE NOW
 COMPLETELY DIFFERENT FROM PLANS/RISER.
 PLEASE SEE RISER SHOWS A 250A MTS. WE
 NEED EITHER SPEC FOR A 250A MTS OR
 REVISE PLANS TO CORRLELATE WITH
 SUBMITTIALS.
 THIS WAS REQUESTED ON THREE PREVIOUS
 REVIEWS AND ONE REVIEW DONE WITH OUT
 PLANS BEING SUBMITTED.
 THIS OFFICE HAS SPOKE TO THE ELECTRICAL
 CONTRACTOR AND THE ELECTRICAL ENGINEER
 ON MORE THAN ONE OCCASION.
 PLEASE KNOW THIS OFFICE HAS ALSO LEFT
 TWO MESSAGES FOR THE ENGINEER ON THE
 OFFICE VOICE MAIL AND THE CELL PHONE
 VOICE MAIL.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  