2006-06-16 00:00:00 | *** UNSAT 2ND REVIEW *** |
| |
| |
| ** PLEASE SEE SOME COMMENTS FROM |
| PREVIOUS REVIEW AND SOME NEW COMMENTS. |
| PLEASE SEE PREVIOUS REVIEW COMMENTS ARE |
| TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH |
| NEW NOTES ADDED AT THE BOTTOM. |
| |
| |
| ******** UNSAT ********* |
| |
| 1) NOTE:NOTE #1 NO, PLEASE SEE ONLY |
| ONE COPY OF SPEC/MANUFACTURES CUT SHEETS |
| WERE SUBMITTED FOR THE GENERATORS. NO |
| SPECS/CUT SHEETS WERE SUBMITTED FOR THE |
| MTS, ATS, FUEL TANK.??? |
| PLEASE SEE SOME ITEMS FOR CODE |
| COMPLIANCE CAN NOT BE VERIFIED AT THIS |
| TIME. |
| ** PLEASE KNOW, TWO COPIES OF ALL MUST |
| BE SUBMITTED. THREE COMPLETE SETS MAY BE |
| SUBMITTED, HOWEVER ONLY TWO ARE |
| REQUIRED. UP TO THREE SETS WILL BE |
| STAMPED. |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SUBMIT ALL MANUFACTURES |
| SPECS/CUT SHEETS FOR GENERATOR, ATS , |
| MTS AND SUB BASE FUEL TANK. |
| PLEASE KNOW, ALL MUST INDICATE LISTING |
| FROM A NRTL. |
| 215.5 |
| |
| 2) NOTE: NOTE #2 OK,HOWEVER PLEASE STILL |
| SEE INFORMATION FOR TANK(S) HAVE NOT |
| BEEN SUBMITTED. |
| |
| 3) NOTE: OK |
| |
| 4) NOTE: OK |
| |
| 5) NOTE: OK.. |
| |
| 6) NOTE: NOTE #6, NO, RISER DOES NOT |
| SHOW THIS AND SPECS WERE NOT SUBMITTED. |
| RESPONSE MENTIONS CIRCUIT BRKR, YET THIS |
| BREAKE RIS SHOWN FROM THE RECEPTS WHICH |
| IS CLEAR AND OK. PLEASE SEE HOWEVER IF |
| SYSTEM IS SET UP ON AN AUTOMATIC |
| TRANSFER A MANUAL MEANS OF DISCONNECT |
| SHALL BE REQUIRED FOR FEEDERS COMING |
| FROM GEN. |
| |
| |
| ** PREVIOUS NOTE ** |
| PLEASE SEE THE MTS MUST CONTAIN |
| A "OFF" POSITION AS THE MEANS OF |
| DISCONNECT REQUIRED FOR POWER COMING |
| FROM THE GEN. THE BRKR ON THE INSIDE OF |
| THE GEN CAN NOT BE THE DISCONNECT MEANS |
| FOR POWER IN EM CONDITIONS. |
| 225.31-225.39. |
| |
| 7) NOTE: OK, AS LT POLE WAS REMOVED FROM |
| PLANS. |
| |
| *** NEW NOTE** |
| |
| 8) NOTE: PLEASE SEE BUILDING NOTE AS |
| FOOTER/WALL/ENCLOSURE/SLAB DETAIL |
| SUBMITTED DOES NOT CONTAIN ANY |
| SIGNATURE,DATE OR SEAL BY THE DESIGNER |
| OF RECORD. |
| PLEASE SEE FS 471.025,481.221 |
| FAC 61G15-23.002 |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY COMMENTS OR |
| QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |