2006-05-16 00:00:00 | ******** UNSAT ********* |
| |
| 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| SPECS/CUT SHEETS FOR GENERATOR, ATS , |
| MTS AND SUB BASE FUEL TANK. |
| PLEASE KNOW, ALL MUST INDICATE LISTING |
| FROM A NRTL. |
| 215.5 |
| |
| 2) NOTE: PLEASE CORRELATE PLANS |
| SUBMITTED. PLEASE SEE ONE SET INDICATES |
| A 100 GAL TANK, AND THE OTHER 500 GAL |
| TANK?? |
| |
| 3) NOTE: PLEASE SEE PLANS SHALL |
| REFERENCE THE CURRENT CODES IN EFFECT |
| AS, THE "LATEST EDITION" MAY NOT BE |
| ADOPTED AT THIS TIME. |
| WORK, PER 2002 NFPA-70, 2002 NFPA-110 |
| 2004 FBC. |
| |
| 4) NOTE: PLEASE CLARIFY FEED TO THE 250A |
| DISC FOR MTS SHOWING 3- 200A RECEPTS?? |
| THE THREE RECEPTS ARE UNCLEAR. PLEASE |
| ALSO SEE ALL DISCONNECTS, MAINS ETC ARE |
| SHOWN AS 250A'S, YET THESE RECEPTS ARE |
| SHOWN AS 200A'S? |
| PLEASE SEE THE LOADS SHOWN SEEM TO BE |
| OVER THE RATINGS OF THE 200A RECEPT? |
| 215.5 |
| |
| 5) NOTE: PLEASE VERIFY TAPPED CONDUCTORS |
| AS SHOWN PER 240.21, LENGTH? |
| PLEASE SEE 450.3 FOR MAX OCP AT 125%. |
| WHEN THE OCP DOES NOT CORRELATE, IT IS |
| PERMITTED TO GO TO THE NEXT STANDARD |
| SIZE PER 240.6. (25A'S). |
| SHOWS 40A'S. |
| |
| 6) NOTE: PLEASE SEE THE MTS MUST CONTAIN |
| A "OFF" POSITION AS THE MEANS OF |
| DISCONNECT REQUIRED FOR POWER COMING |
| FROM THE GEN. THE BRKR ON THE INSIDE OF |
| THE GEN CAN NOT BE THE DISCONNECT MEANS |
| FOR POWER IN EM CONDITIONS. |
| 225.31-225.39. |
| |
| 7) NOTE: PLEASE SEE BLDG REVIEW, AS THE |
| WIND LOAD CALCUALTIONS ARE REQUIRED AT |
| THIS TIME FOR NEW LT POLE(S). |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY COMMENTS OR |
| QUESTIONS, PLEASE DO NOT HESITATE IN |
| CONTACTING THIS OFFICE. |
| |