Plan Review Notes
Plan Review Notes For Permit 06050448
Permit Number 06050448
Review Stop E
Sequence Number 1
Notes
Date Text
2006-05-16 00:00:00******** UNSAT *********
  
 1) NOTE: PLEASE SUBMIT ALL MANUFACTURES
 SPECS/CUT SHEETS FOR GENERATOR, ATS ,
 MTS AND SUB BASE FUEL TANK.
 PLEASE KNOW, ALL MUST INDICATE LISTING
 FROM A NRTL.
 215.5
  
 2) NOTE: PLEASE CORRELATE PLANS
 SUBMITTED. PLEASE SEE ONE SET INDICATES
 A 100 GAL TANK, AND THE OTHER 500 GAL
 TANK??
  
 3) NOTE: PLEASE SEE PLANS SHALL
 REFERENCE THE CURRENT CODES IN EFFECT
 AS, THE "LATEST EDITION" MAY NOT BE
 ADOPTED AT THIS TIME.
 WORK, PER 2002 NFPA-70, 2002 NFPA-110
 2004 FBC.
  
 4) NOTE: PLEASE CLARIFY FEED TO THE 250A
 DISC FOR MTS SHOWING 3- 200A RECEPTS??
 THE THREE RECEPTS ARE UNCLEAR. PLEASE
 ALSO SEE ALL DISCONNECTS, MAINS ETC ARE
 SHOWN AS 250A'S, YET THESE RECEPTS ARE
 SHOWN AS 200A'S?
 PLEASE SEE THE LOADS SHOWN SEEM TO BE
 OVER THE RATINGS OF THE 200A RECEPT?
 215.5
  
 5) NOTE: PLEASE VERIFY TAPPED CONDUCTORS
 AS SHOWN PER 240.21, LENGTH?
 PLEASE SEE 450.3 FOR MAX OCP AT 125%.
 WHEN THE OCP DOES NOT CORRELATE, IT IS
 PERMITTED TO GO TO THE NEXT STANDARD
 SIZE PER 240.6. (25A'S).
 SHOWS 40A'S.
  
 6) NOTE: PLEASE SEE THE MTS MUST CONTAIN
 A "OFF" POSITION AS THE MEANS OF
 DISCONNECT REQUIRED FOR POWER COMING
 FROM THE GEN. THE BRKR ON THE INSIDE OF
 THE GEN CAN NOT BE THE DISCONNECT MEANS
 FOR POWER IN EM CONDITIONS.
 225.31-225.39.
  
 7) NOTE: PLEASE SEE BLDG REVIEW, AS THE
 WIND LOAD CALCUALTIONS ARE REQUIRED AT
 THIS TIME FOR NEW LT POLE(S).
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY COMMENTS OR
 QUESTIONS, PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]