Plan Review Notes
Plan Review Notes For Permit 06050352
Permit Number 06050352
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-29 00:00:00 
  
 DENIED
  
 1) SIGNED AND SEALED ENGINEERING IS
 REQUIRED FOR BUILDINGS OVER 60 FT IN
 HEIGHT PER 1609.1 FBC (SEE EXEPTION# 1)
  
 2) WHERE POSSIBLE WE REQUIRE THE STATE
 OF FLORIDA PRODUCT APPROVAL COVER SHEETS
 PLEASE SUBMIT (FL# 251-R3) FOR SGD-830
 AND (FL# 261-R2) FOR 1X HEAVY MULLIONS
  
 3) THE STATE DOES NOT COVER THE SH-800
 BUT WE WILL ACCEPT MIAMI-DADE NOA FOR
 LOCAL PRODUCT APPROVAL (SEE NOA#
 04-0722.03 WHICH REVISES 02-0719.05
 SH-800 MID-RISE)
  
 4) PLEASE BE ADVISED THAT THE SGD NOA IS
 NON IMPACT AND CANNOT BE USED BELOW 60
 FT. SEE 1609.1.4(1)&(2) FBC. GLAZED
 OPENINGS BETWEEN GRADE ANG 30 FT REQUIRE
 LARGE MISSILE PROTECTION AND GLAZED
 OPENINGS FROM 30 TO 60 FT WILL REQUIRE
 SMALL MISSILE PROTECTION. IF NEEDED ALL
 3 PRODUCTS ARE COVERED UNDER FL#
 251-R3BUT EACH HAS SPERATE MIAMI-DADE
 NOA
  
 5) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO A
 PERMIT BEING ISSUED
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716
  
  