Plan Review Notes
Plan Review Notes For Permit 06050324
Permit Number 06050324
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-08 00:00:00 
 1) THE SYSTEM SELECTED STATES GENERAL
 LIMITATION #7. GENERAL LIMITATION #7
 REQUIRES CALCULATIONS PREPARED, SIGNED
 AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER/ARCHITECT OR ROOF
 CONSULTANT. THE CALCULATION SHALL
 INDICATE HOW THE ROOF PRESSURES WILL
 MEET THE MINIUM REQUIRED PRESSURE OF
 89PSF IN ZONE '3'.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL:(561)805-6726