Plan Review Notes
Plan Review Notes For Permit 06050263
Permit Number 06050263
Review Stop B
Sequence Number 1
Notes
Date Text
2006-05-27 00:00:00 
  
 DENIED
  
 1) DRAWING DOES NOT SHOW ANY DOUBLE HUNG
 WINDOWS PLEASE VERIFY
  
 2) PRODUCT APPROVALS FOR PGT SH WINDOWS
 ARE OLD (2001) PLEASE UPDATE AS NOA'S
 ARE ALSO OUTDATED.
  
 3) WHERE UNITS ARE STACKED TOGETHER
 MULLIONS ARE REQUIRED. SUBMIT PRODUCT
 APPROVALS FOR PGT MULLIONS FOR SINGLE
 HUNG UNITS (SEE FL# 261) AND MARVIN
 MULLIONS FOR CASEMENT UNITS (SEE FL#
 6627) PLEASE MAKE SURE TO MARK
 APPROPRIATE MULLIONS AS SOME MAY NOT
 MEET PRESSURES
  
 4) CASEMENT WINDOW SIZES ARE NOT LISTED
 ON DRAWING PLEASE CORRECT
  
 5) PLEASE SHOW WHERE ARCHED TOP FIWED
 UNITS ARE BEING USED
  
 ADRIAN MORSE
 BLDG PLAN REVIEW
 561-805-6716