Plan Review Notes For Permit 06050232 |
Permit Number |
06050232 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2006-05-31 00:00:00 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBC FLORIDA BUILDING CODE 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS | | TO THE FBC2004 | | | | 1.)31.2 WAS CIRCLED ON THE PRODUCT | | APPROVAL SPECIFICATION.THIS PRESSURE | | IS TOO LOW FOR 140MPH, FBC TABLE | | 1609.6B. | | | | 2.)INDICATE ON THE PRODUCT APPROVAL OR | | ON THE INSTALLATION SCHEDULE WHICH | | CONNECTION TYPE YOU ARE USING AS NOT ALL | | OF THEM ARE COMPLIANT FOR THE ANCHOR | | SPACING YOU HAVE SPECIFIED (12"/12"). |
|