2006-05-23 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE ELECTRICAL CONTRACTOR WILL HAVE
 THIS SYSTEM ENGINEERED OR ACT AS THE
 DESIGNER OF RECORD UNDER THE EXEMPTION
 OF 471 FS.
 IT IS A VIOLATION OF 481 FS TO USE THE
 ARCHITECTS DRAWING WITHOUT HIS APPROVAL
 AND SEAL.
  
 WHEN DRAWING THE PLAN, THE THE
 CONTRACTOR MUST PRINT AND SIGN HIS NAME
 TO SAME.
 SHOW COMPLIANCE WITH NFPA-780.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  